ATTENTION!
Danger of damage to the inverter or derating!
The mounting location must satisfy the following conditions:
The mounting location and immediate environment are permanently fixed, vertical, flat,
non-inflammable and not subject to constant vibration.
The permissible ambient conditions are conformed to; see Technical data
Ä Inverter,
p. 133
et seqq.
The following free spaces must be present around the inverter:
Above/below: at least 200 mm
At the sides/in front: at least 60 mm
Do not install the inverter in areas where animals are kept.
Observe the connection ratings specified on the type plate.
The DC cables must not be connected to an earth potential (DC inputs and AC output are not
galvanically isolated).
ATTENTION!
When transmitting data over a public network:
Transmitting data over a public network can incur additional costs.
Data transmitted over a public network is not protected from unauthorised access by third-
parties.
Note
Avoid exposing the inverter to direct sunlight.
The display must be readable on the installed device.