User manual

Note
With a mains grid voltage of 100 V ... 127 V, the inverter can be connected between the L1, L2
and L3 external conductors as follows:
2-phase mains grids
N and L are connected between the L1 – L2 external conductors at the inverter side. See
and in Fig. 7.
One of the two connected external conductors is connected to PE at the inverter side. This
connection can be made within the AC plug or in an external junction box.
Fig. 7 shows an example of an inverter-side connection between L1 and PE:
Above: connection in an AC plug
Below: Connection in an external junction box )
3-phase mains grids
N and L are connected between the L1 – L2 or L1 – L3 or L2 – L3 external conductors at the
inverter side.
Connect the external conductor on the inverter side to PE: as above.
Fig. 7 as above.
The external conductor voltages are shown in Fig. 8.
1. Wire the AC plug supplied to match the selected external conductors, as described in the
Appendix under Mounting AC plugs. Do not yet close the AC plug.
2. Connect one of the two connected phases to PE at the inverter side. Make this connection
inside the AC plug or use an external junction box, as shown in
Fig. 7.
Fig. 7: Connection of N and PE in the AC plug (above) or junction box (below)
Connection cable between N and PE with the connection point inside the AC plug
External conductor L1
External conductor L2
Connection cable between N and PE with the connection point inside the junction box
Casing of the AC plug
Junction box
GB
747.431 | Z08 | 2014-01-31
106