17.6 Data tables
DHC-E 3/3.5-1 Trend DHC-E 4/6-2 Trend
Item no. 200057 200061
Electrical data
Phase (50/60 Hz) 1/N/GND 1/N/GND | 2/GND
Rated voltage 120 V 240 V 208 V
Rated output
1
, jumper position 1 [low] / 2 [high] 3.0 kW / 3.5 kW 3.8 kW / 6.0 kW 2.9 kW / 4.5 kW
Amperage draw, jumper position 1 [low] / 2 [high] 25 A / 29.2 A 15.8 A / 25 A 13.9 A / 21.7 A
Min. recommended circuit breaker size
2
, jumper position 1 [low] / 2 [high] 25 A / 30 A 20 A / 25 A 15 A / 25 A
Min recommended wire size
3
(copper), jumper position 1 [low] / 2 [high] 10/2 AWG / 10/2 AWG 12/2 AWG / 10/2 AWG 14/2 AWG / 10/2 AWG
Min. resistivity ρ15 ≥ 1100 Ω cm
Max. conductivity ı15 ≤ 910 μS/cm
Connections
Water connections ½˝ NPT
Application limits
Maximum permissible pressure 145 psi (1 MPa)
Maximum inlet temperature for reheating 131 °F (55 °C)
Maximum inlet temperature 149 °F (65 °C)
User selectable temperature range 68–140 °F (20–60 °C)
Internal anti-scalding protection temperature limiter values 100/109/122/140 °F (38/43/50/60 °C)
Hydraulic data
Minimum water flow to activate unit 0.264 gal (1.0 l/min)
Nominal water volume 0.07 gal (0.277 l)
Other
Type of installation Over-sink/under-sink
Protection class 1
Insulating block Glass-reinforced polyamide
Heating system Direct Coil
Cover and back panel Plastic
Color White
Dimensions
Height 14
1
/
8
˝ (360 mm)
Width 8˝ (202 mm)
Depth 4
5
/
16
˝ (109 mm)
Weights
Weight 5.5 lbs (2.5 kg)
DHC-E 3/3.5-1 Trend ships with a 0.5 gpm (1.9 l/min) pressure compensating flow-reducer/aerator that must be installed.
DHC-E 4/6-2 Trend ships with 2 x 0.5 gpm (1.9 l/min) and a 1.0 gpm (3.8 l/min) pressure compensating flow-reducer/aerator that must be installed. See section 11.3, “Aerator
installation at connected faucet,” pg. 17 for more information.
1
Factory default setting is jumper position 2 [high]
2
Overcurrent protection sized at 100% of load. Tankless water heaters are considered a non-continuous load. Use only GFCI Class A circuit breakers.
3
Copper conductors with a temperature rating of 75 °C or greater must be used. Conductors should be sized to maintain a voltage drop of less than 3% under load.
These are our recommendations. Check local codes for compliance if necessary.