5 Operating instructions in accordance with the 2014/68/EU Pressure Equipment Directive
The SRT 15-80 AC 115V T cUL compressed-air refrigeration dryer contains pressure equipment in the sense of the
2014/68/EU Pressure Equipment Directive. Therefore, the entire plant needs to be registered with the supervisory
authority if required in accordance with the local regulations.
For the examination prior to the start-up and for periodic inspections, the national regulations need to be observed, such
as the industrial safety regulation in the Federal Republic of Germany. In countries outside the EU, the respective
regulations in force there need to be adhered to.
The proper use of pressure devices is the basic requirement for safe operation. As regards pressure devices, the
following points need to be observed:
The SRT 15-80 AC 115V T cUL compressed-air refrigeration dryer must only be employed within the pressure and
temperature range limits indicated by the manufacturer on the name plate.
No welding must be carried out on the pressure parts.
The SRT 15-80 AC 115V T cUL compressed-air refrigeration dryer must neither be installed in insufficiently ventilated
rooms nor near heat sources or inflammable substances.
To avoid fractures resulting from material fatigue, the refrigeration dryer should not be exposed to vibrations during
operation.
The maximum operating pressure indicated by the manufacturer on the name plate must not be exceeded. It is the
installer's responsibility to install the appropriate safety and control devices. Prior to the start-up of the SRT 15-80
AC 115V T cUL compressed-air refrigeration dryer, the connected pressure generator (compressor etc.) must be set
to the max. permissible operating pressure. The integrated safeguard needs to be checked by an approved
inspection agency.
The documents related to the SRT 15-80 AC 115V T cUL compressed-air refrigeration dryer (manual, operating
instructions, manufacturer's declaration etc.) must be kept safe for future reference.
No objects whatsoever must be installed at or placed on the SRT 15-80 AC 115V T cUL compressed-air refrigeration
dryer and the connecting lines.
Installation of the plant in frost-free places only.
Operation of the plant is only permissible with fully closed and intact housing and cover panels. Operation of the
plant with damaged housing/cover panels is prohibited.
6 Transport
Check the packaging for visible loss or damage. If no visible damage can be ascertained, place the unit near the place
of installation and unpack the device.
During this procedure, the dryer must always remain in an upright position. The components may be damaged when the
unit is tilted or turned upside down.
Store the device in a dry environment and do not expose it to extreme weather conditions.
Handle with care. Strong shocks can cause irreparable damage.
7 Storage
Keep the device away from extreme weather conditions
even when packaged.
Keep the dryer in an upright position, also while it is stored.
Tilting the device or turning it upside down can cause
irreparable damage to some components.
When the dryer is not in use, it can be stored in its
packaging in a dust-free and protected place at a
temperature of +34°F +122°F (+1°C…+50°C) and at a
specific humidity of max. 90%. If the storage period
exceeds 12 months, you should contact the manufacturer.