SYMPTOM
POSSIBLE CAUSE - SUGGESTED ACTION
Excessive
pressure drop
within the dryer.
The dryer doesn’t drain the condensate - see specific point.
The DewPoint is too low - the condensate is frost and blocks the air - see specific point.
Check for throttling the flexible connection hoses.
The dryer doesnt
drain the
condensate
The condensate drain service valve is closed - open it.
Condensate strainer is clogged remove and clean it.
The drain solenoid valve is jammed remove and clean it.
Verify the electric wiring.
The coil of the drain solenoid valve is failed replace it.
Electronic instrument is faulty replace it.
The DewPoint is too low - the condensate is frost and blocks the air - see specific point.
Inlet compressed air pressure is too low and condensate is not drained restore nominal
conditions.
The dryer
continuously
drains
condensate.
The drain solenoid valve is jammed remove and clean it.
Try to remove the electric connector on the solenoid valve - if drain stops verify the electric
wiring or the electronic instrument is faulty - replace it
Water within the
line.
The dryer doesn't start - see specific point.
If installed - Untreated air flows through the by-pass unit - close the by-pass.
The dryer doesn’t drain the condensate - see specific point.
DewPoint too high - see specific point.
DMC35 -
Led and
display 1st (left)
and 10th (right)
led are flashing.
Verify the electric wiring of BT1 DewPoint probe.
The BT1 DewPoint probe is faulty - replace it.
The electronic instrument is faulty - replace it.
DMC35
Led and
led are
flashing
Verify the electric wiring of BT2 fan control probe.
The BT2 fan control probe is faulty - replace it.
The electronic instrument is faulty - replace it.
DMC35
Led and
display 1st (left)
led are flashing
DewPoint too low - see specific point.
The BT1 DewPoint probe is faulty - replace it.
The electronic instrument is faulty - replace it.
DMC35
Display 10th
(right) led is
flashing
DewPoint too high - see specific point.
The BT1 DewPoint probe is faulty - replace it.
The electronic instrument is faulty - replace it.