The dryer does not discharge the condensate see the corresponding point.
The hot-gas bypass valve needs to be re-adjusted contact a SULLAIR service technician to have the
nominal setting re-established.
There is a leak in the refrigeration cycle contact a SULLAIR service technician.
Dew point too low.
SR 10-100 - The fan is always ON - the yellow LED of DMC15 electronic instrument is flashing - see
specific point
SR 125-480 - The fan runs continuously the PV pressure switch is defective replace it.
The ambient temperature is too low re-establish the nominal conditions.
The hot-gas bypass valve needs to be re-adjusted contact a SULLAIR service technician to have the
nominal setting re-established.
Extreme pressure
drop in the dryer.
The dryer does not discharge the condensate see the corresponding point.
The dew point is too low the condensate is frozen and blocks the air see the corresponding point.
Check the flexible connection hoses for obstructions.