The method below should be applied during the first start-up, after longer downtimes or subsequent to
maintenance works.
The start-up must be carried out by certified skilled personnel.
Processing sequence (see Section 11.1 "Control panel")
• Ensure that all the steps of the “Installation” chapter have been observed.
• Ensure that the connection to the compressed air system is correct and that the piping is suitably fixed and
supported.
• Ensure that the condensate drain pipe is properly fastened and connected to a collection system or container.
• Ensure that the by-pass system (if installed) is open and the dryer is isolated
• Ensure that the manual valve of the condensate drain circuit is open.
• Remove any packaging and other material which could obstruct the area around the dryer.
• Activate the mains switch.
• Turn on the main switch - pos. 1 on the control panel.
• Ensure that the electronic instrument DMC14 is ON.
• Ensure the consumption matches with the values of the data plate.
• Ensure the fan work properly - wait for its first interventions (Air-Cooled).
• Allow the dryer temperature to stabilise at the pre-set value.
• Slowly open the air inlet valve.
• Slowly open the air outlet valve.
• Slowly close the central by-pass valve of the system (if installed).
• Check the piping for air leakage.
• Ensure the drain is regularly cycling - wait for its first interventions.