Product Manual

Form #43219020
5 June 09
MINIMUM CLEARANCES TO COMBUSTIBLES
Mounted Horizontally Mounted at 35º Angle
BELOW BELOW FRONT
MODEL SIDES CEILING
w/Standard
Reflector
w/Reflector
Extension
w/Standard
Reflector
w/Reflector
Extension
w/Standard
Reflector
w/Reflector
Extension
REAR
Angle
Mounting
SG3 and SG4
31” 37” 73” 101” 73” 101” 37” 51” 31”
(degree)
0º min
35º max
SG6 and SG8
49” 49” 99” 138” 99” 138” 49” 69” 37”
0º min
35º max
SG10 and SG12
49” 65” 129” 181” 129” 181” 61” 85” 49”
0º min
35º max
SG13,SG14 and
SG15
61” 65” 137” 191” 137” 191” 65” 91” 49”
10º min
35º max
NOTE
: The clearances specified above must be maintained to combustibles and other materials that may be
damaged by temperatures 90ºF above ambient temperature. It is the installer’s responsibility to ensure that
building materials with a low heat tolerance which may degrade at lower temperatures are protected to
prevent degradation. Clearances to combustibles are posted on the reflector near the control end of the heater.
In locations used for storage of combustible materials where they may be stacked below the heater, NFPA 54
requires that the installer must post signs that will “specify the maximum permissible stacking height to
maintain the required clearances from the heater to combustibles.” SunStar recommends posting these signs
adjacent to the heater thermostat or other suitable location that will provide enhanced visibility.
5) SG SERIES SPECIFICATIONS
ORIFICE SIZE
7
MODEL NO. BTU/HR INPUT
NUMBER
OF BURNERS
Natural Gas Propane Gas
SHIPPING WEIGHT
MINIMUM
MOUNTING
HEIGHTS (FEET)
SG3-N5B 33,000 1 3/32” n/a 30 lbs. 12
SG4-N5B 40,000 1 #38 n/a 30 lbs. 12
SG6-N5B 65,000 2 3/32” n/a 35 lbs. 13
SG8-N5B 80,000 2 #38 n/a 35 lbs. 14
SG10-N5B 100,000 3 #41 n/a 48 lbs. 15
SG12-N5B 120,000 3 #38 n/a 48 lbs. 16
SG14-N5B 140,000 4 #41 n/a 58 lbs. 17
SG15-N5B 155,000 4 #38 n/a 58 lbs. 18
SG3-L5B 32,000 1 n/a #52 30 lbs. 12
SG6-L5B 65,000 2 n/a #52 35 lbs. 13
SG10-L5B 100,000 3 n/a #52 48 lbs. 15
SG13-L5B 140,000 4 n/a #52 58 lbs. 17
MODEL SUFFIX
Gas Type: Ignition System:
GAS-PIPE
CONNECTION:
N = Natural
L = Propane 5 = Direct Spark (115 Volt / 0.40 Amp / 60 Hz)
1/2” NPT (Female)
7
One Orifice Per Burner
*MOUNT HEATERS AS HIGH AS POSSIBLE. Minimums are shown as a guideline for human comfort and
uniform energy distribution for complete building heating applications. Consult your SunStar representative
for the particulars of your installation requirements.