Product Manual

–10– Form #43219030
June 09
11) THERMOSTAT WIRING INSTALLATIONS
TH
PP
TH
PP
Powerpile
Thermostat
Power Unit Coil
Operator
Coil
Valve @ Heater
Pilot
Powerpile
(Generator)
Cartridge
Model No. Suffix: N1, L1
Self Generating,
Millivolt Standing Pilot
(Single Heater Per Thermostat)
*
* CAUTION: A millivolt type thermostat
is required for use on
self-generating pilot
model heaters N1 & L1.
12) VENTILATION
Failure to do so may result in death, serious injury, property
damage or illness from Carbon Monoxide poisoning.
Heaters installed in an unvented mode require a minimum
ventilation flow of 4 CFM per 1,000 Btu/hr of total installed
capacity.
CARBON MONOXIDE HAZARD
Where unvented infrared heaters are used, natural or mechanical means shall be provided to supply and exhaust
at least 4 cfm per 1000 Btu per hr input of installed heaters.
Exhaust openings for removing flue products shall be above the level of the heaters.
This heater requires ventilation in the building to dilute the product of combustion and provide fresh air for
efficient combustion. Power ventilation is recommended, and the minimum vent flow required is as follows:
SGM3 = 109 cfm SGM6 = 218 cfm SGM10 = 436 cfm
If gravity ventilation is used, the required square feet of inlet and outlet vent area (depending on height and
temperature difference) is as follows:
SGM3 = 0.4 s/f SGM6 = 0.8 s/f SGM10 = 1.6 s/f
The General Ventilation Rules outlined in the ASHRAE GUIDE AND DATA BOOK should be observed when locating
vents. Exhaust vents must be located at the highest point above and in the vicinity of the heaters and the inlet
nets must be located below the level of the heaters.