Product Manual

–5– Form #43219030
June 09
MOUNTED HORIZONTALLY
BACK SIDES CEILING BELOW
MODEL
BACK
BACK
w/Reflector
Extension SIDES
SIDES
w/Reflector
Extension CEILING
CEILING
w/Reflector
Extension BELOW
BELOW
w/Reflector
Extension
SGM3 24” 36” 24” 36” 24” 36” 48” 126”
SGM6 36” 36” 30” 36” 36” 36” 72” 126”
SGM10 45” 48” 48” 60” 36” 36” 96” 168”
MOUNTED at 45º ANGLE
BACK SIDES CEILING BELOW
MODEL
BACK
BACK
w/Reflector
Extension SIDES
SIDES
w/Reflector
Extension CEILING
CEILING
w/Reflector
Extension BELOW
BELOW
w/Reflector
Extension
SGM3 8” 12” 24” 36” 32” 36” 48” 126”
SGM6 12” 12” 30” 36” 36” 36” 72” 126”
SGM10 18” 12” 48” 60” 36” 36” 96” 168”
! IMPORTANT
: The clearances specified above must be maintained to combustibles and other materials that may
be damaged by temperatures 90ºF above ambient temperature. It is the installer’s responsibility to ensure that
building materials with a low heat tolerance which may degrade at lower temperatures are protected to prevent
degradation. Clearances to combustibles are posted on the reflector near the control end of the heater. In areas
used for storage of combustible materials where they may be stacked below the heater, NFPA54 requires that the
installer must post signs that will "specify the maximum permissible stacking height to maintain the required
clearances from the heater to combustibles." SunStar recommends posting these signs adjacent to the heater
thermostat or other suitable location that will provide enhanced visibility.
5) SGM SPECIFICATIONS
MODEL
GAS
TYPE
INPUT
BTU/HR
MINIMUM
MOUNTING HEIGHT*
ORIFICE
SIZE
SHIPPING
WEIGHT
SGM3-N1 Natural 26,000 12 ft. #42 (0.0935) 30 lbs.
SGM3-L1 Propane 26,000 12 ft. #53 (0.0595 30 lbs.
SGM6-N1A Natural 52,000 14 ft. #32 (0.1160) 40 lbs.
SGM6-L1 Propane 52,000 14 ft. #45 (0.0820) 40 lbs.
SGM10-N1A Natural 104,000 15 ft. #32 (0.1160) 70 lbs.
SGM10-L1 Propane 104,000 15 ft. #45 (0.0820) 70 lbs.
MODEL SUFFIX:
Gas Type: Ignition System:
REFLECTOR TYPE:
GAS-PIPE
CONNECTION:
N = Natural
L = Propane
1 = Standing Pilot (Millivolt)
Standard or
Optional Parabolic Reflector Extension 1/2" NPT (Female)
*MOUNT HEATERS AS HIGH AS POSSIBLE. Minimums are shown as a guideline for human comfort and
uniform energy distribution for complete building heating applications. Consult your SunStar representative
for the particulars of your installation requirements.