Specification

Lamps
LPX Series Exits use energy efficient, long life
LED’s to provide uniform diffuse illumination of
the exit face. These red and green LEDs require
no maintenance and consume less than one
watt, on average.
Housing Construction
Rugged, durable, injection molded
polycarbonate materials are used throughout
the LPX Series Exits. All structural components
are designed with reinforcing ribs to add
additional rigidity and to maximize structural
integrity. These materials are impact and scratch
resistant, and they have been UV stabilized to
resist discoloration due to age and ultraviolet
radiation. All components are designed to be of
snap-fit construction - no mechanical fasteners –
to facilitate installation in under 5-minutes. Any
components required for installation (wirenuts,
wire leads, universal metal J-box bracket, etc.)
are all included with each exit. The universal
design of the LPX Series Exits enables universal
exits to be configured as single face or double
face in the field. All LPX Series Exits can be wall,
ceiling, or end mounted; a rugged, snap-fit, low
profile canopy with captive screws is included
with every exit for ceiling and end mounting
applications.
Lens
Lenses for the LPX Series Exits are made from
durable, impact resistant polycarbonate. All exit
faces are designed with full 3/4” stroke snap-
out or snap-in chevron directional indicators to
insure maximum visibility and compliance with
the latest codes. Units come with red lenses
installed and green lenses included for field
selectable red or green signs.
Sure-Lites EZ Key External Battery
Disconnect (Self Powered Only)
Patented technology that allows installers to
externally control the battery connection. Better
than line latching, allows installers to choose
when the battery is connected so that it stays
fresh longer. Allows battery to be disconnected
after installation but before building is occupied,
enabling emergency circuit to be shut down for
power savings.
Brownout Circuit (Self Powered Only)
The brownout circuit on Sure-Lites’ exits
monitors the flow of AC current to the exit and
activates the emergency lighting system when
a predetermined reduction of AC power occurs.
This dip in voltage will cause most ballasted
fixtures to extinguish causing loss of normal
lighting even though a total power failure has
not occurred.
Solid-State Transfer (Self Powered Only)
The LPX Series Exit incorporates solid-state
switching which eliminates corroded and pitted
contacts or mechanical failures associated with
relays. The switching circuit is designed to
detect a loss of AC voltage and automatically
energizes the lamps using DC power. Upon
restoration of AC power, the DC power will be
disconnected and the charger will automatically
recharge the battery.
Low Voltage Disconnect (Self Powered Only)
When the battery’s terminal voltage falls, the
low-voltage circuitry disconnects the lighting
load. The disconnect remains in effect until
normal utility power is restored, preventing
deep battery discharge.
Test Switch/Power Indicator Light (Self
Powered Only)
A test switch located on the side of the exit
permits the activation of the emergency circuit
for a complete operational systems check. The
Power Indicator Light provides visual assurance
that the AC power is on.
Sealed Nickel Cadmium Battery (Self
Powered Only)
Sure-Lites sealed nickel cadmium batteries are
maintenance-free with a life expectancy of 10
years. The sealed rechargeable nickel cadmium
battery offers high discharge rates and stable
performance over a wide range of temperatures,
from 0-40¡ C.
“2C” (AC Only)
The “2C” Option enables the Exits to operate
per the requirements of UL 924 when connected
simultaneously to both normal and emergency
power circuits (two circuit operation–UL
Category FTBR–Emergency Lighting and Power
Equipment). The “2C” Option is a factory
assembly change which alters the standard
Exit such that it complies with and is UL Listed
under the FTBR Category. This option should
only be used for exits which are intended to
be connected simultaneously to normal and
emergency power circuits. Both circuits have
universal 120/277 VAC standard.
Self Diagnostics Option (Self Powered Only)
The self-diagnostic unit will automatically
perform all tests required by UL924, and NFPA
101. The system indicates the status of the exit
at all times using the LED indicator near the
test switch on the side of the unit. A 90 minute
battery power (emergency mode) simulation
test will occur randomly once every 12 months.
A 30 second battery power simulation test will
occur every 30 days.
DLVP
Distributed Low-Voltage Power (DLVP) is a
system which embraces an AC line voltage
backbone for transmission and low voltage
DC for connectivity in a space. The DLVP
architecture allows for a fast and simple
installation and configuration without sacrificing
electrical efficiencies of line voltage LED
fixtures. DLVP blends the benefits of both AC
and DC power distribution to reduce the total
installed cost of a lighting project by up to
20% while providing a completely flexible and
electrically efficient solution. The DLVP option is
enabled with a field installable kit.
Warranty
All Sure-Lites’ products are backed by a firm
five-year warranty against defects in material
and workmanship. Maintenance-free, long-life,
sealed nickel cadmium batteries carry a seven-
year pro-rata warranty.
TECHNICAL DATA
LPX SERIES
Eaton
1121 Highway 74 South
Peachtree City, GA 30269
P: 770-486-4800
www.eaton.com/lighting
Specifications and
dimensions subject to
change without notice.
TD505112EN