Specification

Sure-Lites
LPX/LPXC SERIES
TD505032EN
2017-9-6
Eaton
1121 Highway 74 South
Peachtree City, GA 30269
P: 770-486-4800
www.eaton.com/lighting
Specifications and
dimensions subject to
change without notice.
SELF DIAGNOSTIC TESTING OPERATIONS
The Sure-Lites Eagle Eye Self Diagnostics is continuously monitoring your emergency fixture, and will signal any failure through the 3 color
indicator LED.
Initial Operation:
When the unit is first powered up it will go into a 24 hour fast charge and the indicator LED will pulse green. Once the unit has fully charged it
will perform a self calibration. After self calibration, the LED will change to steady green indicating the unit is fully charged and float charging
the battery to maintain readiness.
Automatic Testing:
The unit will perform a battery capacity, lamp/LED, and charge circuit test every 30 days for 30 seconds. During this time, the indicator LED will
change to a steady yellow. It will perform a full battery capacity (90 minute) test once per year. During this time, the indicator LED will change to
a blinking yellow.
Manual Testing:
10 Second “Installation” test – Press and release the test button once during fast charge (blinking green) to initiate a 10 second quick test. The
sign will switch to emergency mode for 10 seconds allowing the installer to verify proper installation of the unit, and the LED indicator will
turn solid yellow.
30 Second Test - Press and release the test button once during float charge (steady green). The indicator LED will turn steady yellow to
indicate the unit is performing a 30 second test of the batteries and lamps/LEDs.
90 Minute Test - Press and release the test button a second time during a 30 second test (steady yellow) to change to a 90 minute test. During
this test, the LED indicator will change to blinking yellow, and the circuit will perform a full battery capacity, charge circuit, and LED test.
Canceling Test – Press and release the test button during the 90 minute test (flashing yellow) to return the fixture to its original state (fast
charge or float charge)
Laser Test:
The SEL SD products are equipped with a Laser Test function that allows the unit to be manually tested without the need to physically press the
test button. Shining a laser pointer in the hole marked “LASER TEST” on the bottom of the unit has the same effect as a press and release of
the test button.
Clearing Failure Codes:
A battery failure (LED two blink red) can be cleared by replacing the battery. Disconnecting the battery and AC power, or performing a full
90 minute discharge will reset the error code, however, it will return if the battery is faulty
Charge Circuit (LED three blink red) and lamp/LED failure (LED four blink red) will clear when the unit successfully passes a manual or
automatic 30 second test.
SELF DIAGNOSTIC TESTING OPERATIONS
Indicators:
LED Off - No power to unit, emergency mode.
LED Steady Green - Unit is fully charged and is float charging the battery to maintain readiness.
LED Green Pulse - Unit is in a 24 hour fast charge of the battery.
LED Two Blink Red - Battery has failed a capacity test, or the battery is disconnected. See “Clearing Failure Codes” above.
LED Three Blink Red - Battery charge circuit has failed. See “Clearing Failure Codes” above.
LED Four Blink Red - Lamps have burned out, or on an EXIT/Combo, 50% or more of the LEDs have failed. See “Clearing Failure Codes” above.
LED Steady Yellow - 30 second test or 10 second quick test (Fast Charge only).
LED Blinking Yellow - 90 minute test.
Maintenance:
None required. Replace the batteries as needed according to ambient conditions. However, we recommend that the equipment be tested
regularly in accordance with local codes.
OFF - EMERGENCY
MODE / POWER OFF
2 BLINK RED -
BATTERY FAILURE
STEADY GREEN -
FULL / FLOAT
CHARGE
STEADY BLINK YELLOW
- 90 MINUTE TEST
3 BLINK RED - CHARGE
CIRCUIT FAILURE
4 BLINK RED - LAMP/
LED FAILURE
STEADY YELLOW -
QUICK TEST
STEADY BLINK
GREEN - FAST
CHARGE
SURE-LITES