Specification

SELF DIAGNOSTIC TESTING OPERATIONS (CONTINUED)
Emergency Light
SELW
automatic 30 second test
Indicators:
LED Off - No power to unit, emergency mode.
LED Steady Green - Unit is fully charged and is float charging the battery to maintain readiness.
LED Green Pulse - Unit is in a 24 hour fast charge of the battery.
LED Two Blink Red - Battery has failed a capacity test, or the battery is disconnected. See “Clearing Failure Codes” above.
LED Three Blink Red - Battery charge circuit has failed. See “Clearing Failure Codes” above.
LED Four Blink Red - Lamps have burned out, or on an EXIT/Combo, 50% or more of the LEDs have failed. See “Clearing Failure Codes” above.
LED Steady Yellow - 30 second test or 10 second quick test (Fast Charge only).
LED Blinking Yellow - 90 minute test.
Maintenance:
None required. Replace the batteries as needed according to ambient conditions. However, we recommend that the equipment be tested
regularly in accordance with local codes.
OFF - EMERGENCY
MODE / POWER OFF
2 BLINK RED -
BATTERY FAILURE
STEADY GREEN -
FULL / FLOAT
CHARGE
STEADY BLINK YELLOW
- 90 MINUTE TEST
3 BLINK RED - CHARGE
CIRCUIT FAILURE
4 BLINK RED - LAMP/
LED FAILURE
STEADY YELLOW -
QUICK TEST
STEADY BLINK
GREEN - FAST
CHARGE
SURE-LITES
Eaton
1121 Highway 74 South
Peachtree City, GA 30269
P: 770-486-4800
www.eaton.com/lighting
Specifications and
dimensions subject to
change without notice.