Installation Distances
According to the standard EN 1366-2, the minimum distance from the wall or ceiling to the duct that holds PKI-C
is 75 mm. For multiple crossings through a re resistive wall the minimum distance between two ducts that hold
PKI-C is 200 mm. This applies for distances between the duct that holds PKI-C and a nearby foreign object crossing
the re resistive wall (please see Fig. 3 and
Tab. 3 ).
Fig. 3: Installation distances between ducts holding PKI-C damper
75
75
200
200