UserManual PKI Cen GB

4/32 | User Manual PKI-C | 201904 201904 | User Manual PKI-C | 5/32
Operating Conditions
Fire dampers can be dened as re shutters for ventilation ducts in the place where they pass through walls
or ceilings, which are the borders of the re area. In case of re, the dampers function as a re safety element
and by closing, they prevent the re and smoke from expanding through the ventilation duct during the dened time.
The re dampers are intended:
For installation in places which are protected against weather disruptions.
For ducts, distributing air without any mechanical or chemical contamination.
For maximum air ow velocity 6 m/s.
For storage temperature minimum -10°C and maximum 50°C.
List of Accessories
PRC-PKIC-DN: Set of 4 cover boards mandatory for dry installation
TVK-PKIC-DN: Flexible duct connection for PKI-C accessibility
The accessories can be ordered along with the re dampers. “DN ” stands for nominal dimension.
PKI-C re damper is equipped with a thermal fuse which, after reaching or exceeding 72°C (± 2°C),
activates the spring which closes the damper blade.
From the noise perspective all Systemair dampers are passive. Increased noise can only be heard when the damper
is being closed in case of an inspection or re.