Fire Safety Products PKI-C Cartridge Fire Dampers User Manual
/32 | User Manual PKI-C | 201904 Table of Contents Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Operating Conditions . . . . . . . . . . . . . . . . . . . . . 5 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Installation Methods . . . . . . . . . . . . . . . . . . . .
201904 | User Manual PKI-C | 3/32 Introduction This is the original installation, inspection and operating instructions document for PKI-C fire dampers.
/32 | User Manual PKI-C | 201904 Warnings Some damper parts may have sharp edges – therefore to protect yourself from harm, please use gloves during damper installation and manipulation. In order to prevent electric shock, fire or any other damage which could result from incorrect damper usage and operation, it is important to: 1. ensure that installation is performed by a trained person. 2. follow the written and depicted instructions provided within this User Manual closely. 3.
201904 | User Manual PKI-C | 5/32 Operating Conditions Fire dampers can be defined as fire shutters for ventilation ducts in the place where they pass through walls or ceilings, which are the borders of the fire area. In case of fire, the dampers function as a fire safety element and by closing, they prevent the fire and smoke from expanding through the ventilation duct during the defined time. The fire dampers are intended: • For installation in places which are protected against weather disruptions.
/32 | User Manual PKI-C | 201904 Installation • The PKI-C fire damper is installed into the duct, in the place where the fire-proof wall is, or at the end of the duct in front of an air valve or a similar outlet. • The duct that holds the fire damper must be supported or hung in such a way that the crossing does not carry its weight. The crossing must not support any part of the surrounding construction or wall which could cause damage and consequent damper failure.
201904 | User Manual PKI-C | 7/32 Dimension Range (mm) Certificate No.
/32 | User Manual PKI-C | 201904 Opening Preparation for the Rigid Wall + DN 60 1 S Fig. 1: Rigid wall/ceiling with a circular opening Legend 1 Concrete/masonry/cellular concrete Tab.
201904 | User Manual PKI-C | 9/32 Opening Preparation for the Flexible Wall DN +1 00 + DN 4 60 2 3 1 S Fig. 2: Flexible (plasterboard) wall with a circular opening Legend 1 On each side - 2 layers of plasterboard (thickness see Tab. 2) 2 Vertical CW-profiles (profile width sCW based on fire resistivity, see Tab. 2) 3 Horizontal UW-profiles (profile width sCW based on fire resistivity, see Tab. 2) 4 Mineral wool; thickness/cubic density see Tab. 2 Tab.
/32 | User Manual PKI-C | 201904 Installation Distances According to the standard EN 1366-2, the minimum distance from the wall or ceiling to the duct that holds PKI-C is 75 mm. For multiple crossings through a fire resistive wall the minimum distance between two ducts that hold PKI-C is 200 mm. This applies for distances between the duct that holds PKI-C and a nearby foreign object crossing the fire resistive wall (please see Fig. 3 and Tab. 3 ). ≥ 200 ≥ 75 ≥ 75 ≥ 200 Fig.
201904 | User Manual PKI-C | 11/32 Wet Installation Using Plaster/Mortar/Concrete Filling Wet 1. The supporting construction opening must be prepared in a way described in the section “Opening Preparation” (as per Fig. 1 and Fig. 2). Opening surfaces must be even and cleaned off. The flexible wall opening must be reinforced as per the standards for plasterboard walls. 2. For installation purposes, make a round opening with a diameter of DN + 60 mm into the wall (as per Fig. 1 and Fig. 2). 3.
/32 | User Manual PKI-C | 201904 EI60S/EI90S/EI120S - Flexible Wall Wet Installation with Continuous Duct Fig. 4: Wet installation of PKI-C in flexible wall ≥100 (EI60S) ≥125 (EI90S) ≥150 (EI120S) ≥40 (EI60S, EI90S) ≥60 (EI120S) 12,5 (EI60S, EI90S) 15 (EI120S) ≤500 200 DN DN + 60 DN + 100 3 45 max Fig.
201904 | User Manual PKI-C | 13/32 EI60S/EI90S/EI120S - Flexible Wall Installation into the End of a Duct Fitted with Valve 20 ≥40 (EI60S, EI90S) ≥60 (EI120S) Wet ≥100 (EI60S) ≥125 (EI90S) ≥150 (EI120S) 12,5 (EI60S, EI90S) 15 (EI120S) 3 1 DN 1 DN + 60 2 DN + 100 3 4 4 45 max 60 max Fig. 6: Wet installation of PKI-C in flexible wall Fig. 7: Cross-section of Wet installation in flexible wall Legend (Fig. 4 up to Fig.
/32 | User Manual PKI-C | 201904 EI60S/EI90S/EI120S - Rigid Wall Wet Installation with Continuous Duct 4 3 2 1 Fig. 8: Wet installation of PKI-C in rigid wall ≥100 (EI60S) ≥125 (EI90S) ≥150 (EI120S) ≤500 200 DN DN + 60 3 45 max Fig.
201904 | User Manual PKI-C | 15/32 EI60S/EI90S/EI120S - Rigid Wall Installation into the End of a Duct Fitted with Valve 20 Wet ≥100 (EI60S) ≥125 (EI90S) ≥150 (EI120S) 3 3 1 1 DN DN + 60 2 4 4 45 max 60 max Fig. 10: Wet installation of PKI-C in rigid wall Fig. 11: Cross-section of Wet installation in rigid wall Legend (Fig. 8 up to Fig.
/32 | User Manual PKI-C | 201904 EI60S/EI90S/EI120S - Ceiling Wet Installation with Continuous Duct 4 2 3 1 Fig. 12: Wet installation of PKI-C in ceiling ≤500 ≥125 ± 10 (EI60S) ≥150 ± 10 (EI90S, EI120S) 200 4 2 45 max 3 1 DN DN + 60 Fig.
201904 | User Manual PKI-C | 17/32 EI60S/EI90S/EI120S - Ceiling Wet Installation into the End of a Duct Fitted with Valve 2 1 3 4 Fig. 14: Wet installation of PKI-C in ceiling 2 1 20 DN 4 45 max ≥150±10 60 max 3 DN + 60 Fig. 15: Cross-section of Wet installation in ceiling Legend (Fig. 12 up to Fig. 15) 1 Fire damper PKI-C 2 Connected metal ductwork 3 Plaster/mortar/concrete filling 4 Flexible duct coupling TVK-PKIC-DN/return plastic valve (e.g.
/32 | User Manual PKI-C | 201904 Dry Installation Dry Using Mineral Wool and Coverplates “Opening Preparation” 1. The supporting construction opening must be prepared in a way described in the section (as per Fig. 1 and Fig. 2). Opening surfaces must be even and cleaned off. The flexible wall opening must be reinforced as per the standards for plasterboard walls. Insert the open damper into the middle of the opening so that the damper blade is in the wall. 2.
201904 | User Manual PKI-C | 19/32 EI90S/EI120S - Flexible Wall Installation with Continuous Duct 3 5 6 Dry 4 2 7 1 Fig. 16: Dry installation of PKI-C in flexible wall ≥125 (EI90S) ≥150 (EI120S) 10 ≥40 (EI90S) ≥60 (EI120S) 12,5 (EI90S) 15 (EI120S) ≤500 7 6 200 5 DN DN + 60 DN + 100 DN + 120 DN + 170 3 45 max Fig.
/32 | User Manual PKI-C | 201904 EI90S/EI120S - Flexible Wall Dry Installation into the End of a Duct Fitted with Valve 20 10 ≥125 (EI90S) ≥150 (EI120S) ≥40 (EI90S) ≥60 (EI120S) 12,5 (EI90S) 15 (EI120S) 3 5 6 7 2 6 5 1 DN DN + 60 1 DN + 120 7 DN + 170 3 4 4 45 max 60 max Fig. 18: Dry installation of PKI-C in flexible wall Fig. 19: Cross-section of Dry installation in flexible wall Legend (Fig. 40 up to Fig.
201904 | User Manual PKI-C | 21/32 EI90S/EI120S - Rigid Wall Dry Installation with Continuous Duct 3 5 6 7 4 2 1 Fig. 20: Dry installation of PKI-C in rigid wall ≥125 (EI90S) ≥160 (EI120S) 10 ≤500 7 6 200 5 DN DN + 60 DN + 120 DN + 160 3 45 max Fig.
/32 | User Manual PKI-C | 201904 EI90S/EI120S - Rigid Wall Dry Installation into the End of a Duct Fitted with Valve ≥125 (EI90S) ≥160 (EI120S) 20 10 3 5 6 7 6 2 5 DN DN + 60 1 DN + 120 7 DN + 170 3 4 4 45 max 60 max Fig. 22: Dry installation of PKI-C in rigid wall Fig. 23: Cross-section of Dry installation in rigid wall Legend (Fig. 20 up to Fig. 23) 1 Fire damper PKI-C 2 Connected metal ductwork 3 Mineral wool filling (min.
201904 | User Manual PKI-C | 23/32 Electrical Connections IMPORTANT: Danger of electric shock! Switch off the power supply before working on any electrical equipment. Only qualified electricians are allowed to work on the electrical system. Power consumption must be observed. 1. Drill hole in the duct as close to the microswitch as possible and near the wall 2. Insert rubber gland into drilled hole 3. Connect cables according to electrical scheme (Fig. 24 or Fig. 25) Tab.
/32 | User Manual PKI-C | 201904 Operation Manual The fire damper is ready for installation when its blades are in open position. Follow next steps (see Fig. 26): 1. Check the thermal fuse link. Thermal fuse link is inserted only in one blade and both parts of the link hold together. 2. Press both detent springs. 3. Open the blades into a parallel position 4. Press the blades together until the fuse link holds both blades.
201904 | User Manual PKI-C | 25/32 3. C 1 C Open the blades into a parallel position NOTE: 1 = Thermal fuse link 4. D D Put on the thermal fuse link Fig.
/32 | User Manual PKI-C | 201904 Fire Damper Functionality Check 1. While performing the check, focus on the thermal fuse link’s integrity and a correct position of the damper blades after their detention in the OPEN position – they should be roughly parallel to the longitudinal axis of the duct. 2. Perform the damper activity check by taking off the thermal fuse link and releasing the blades to spontaneously close them – the damper blades are closed by a spring return release. 3.
201904 | User Manual PKI-C | 27/32 Warranty Conditions For warranty conditions contact your local Systemair representative. Before you can install the fire damper, it’s functionality must be tested as per chapter “Fire Damper Functionality Check”.
/32 | User Manual PKI-C | 201904 Operating Journal Activation of the Damper Mark the Applied Installation Method with a Cross: Wet Date Dry Description of the Discovered Defects and the Date of the Following Inspection after the Elimination of Deficiencies. Inspection Technician’s Signature NOTE: It is also needed to indicate the applied installation method onto the label on the fire damper.
201904 | User Manual PKI-C | 29/32 Periodic Damper Inspections – at Least Once Every 12 Months Date Description of the Discovered Defects and the Date of the Following Inspection after the Elimination of Deficiencies Inspection Technician’s Signature
/32 | User Manual PKI-C | 201904 Periodic Damper Inspections – at Least Once Every 12 Months Date Description of the Discovered Defects and the Date of the Following Inspection after the Elimination of Deficiencies Inspection Technician’s Signature
201904 | User Manual PKI-C | 31/32 Periodic Damper Inspections – at Least Once Every 12 Months Date Description of the Discovered Defects and the Date of the Following Inspection after the Elimination of Deficiencies Inspection Technician’s Signature
/32 | User Manual PKI-C | 201904 Damper Identification 12 1396 Building Object Systemair Production a.s. 90043 Kalinkovo 371, Slovakia 1396-CPD-0050 PKI-C EN 15650 : 2010 Circular fire dampers Nominal activation conditions/sensitivity: Pass Placement - sensing element load bearing capacity - sensing element response temperature Response delay (response time): Pass Room No.