Installation Manual

Installation
28Page
TheTH2DV/TH2OSEasyLinksystemislimitedupto4units.Ifyouconnect
morethan4units,onlythefirst4unitswillworkasapartoftheEasyLink
system.Theotheradditionalunitswillnotwork.
TheTH2DV/T
H2OScannotbelinkedwithotherdifferentTakagimodelsinan
EasyLinksystem.
EASYLINKSYSTEM
General‐
TheTH2DV/TH2OScanbeconnectedwithotherheatersofthesamemodelwith
communicationcablestoworkasamultipleunitmanifoldsystem.
TheEasyLinksystemallowsupto4unitstomanifoldtogether.
Acommunicationcable(graycolor)comeswitheachunit.
You
canmanifoldfrom2to4unitswithouttheneedforamultisystemcontroller.A4unit
systemhasfullautomaticmodulationbetween13,000BTU/hand796,000BTU/h.
EasyLinkConnectionProcedures‐
1.Verifythesettemperaturesofallunitswithinthesystem.EverysingleTH2DV/TH2OSmustbe
settothesamesettemperature.
2.SelectoneunittobetheMASTERunit.
3.MASTERunit
Locatethetwobanks ofdipswitchestotheleftofthe3digit7seg.LEDonthecomputerboardof
theTH2DV/TH2OSthatyouselecttobetheMASTERunit.ChangedipswitchNo.10onthe
rightbankofdipswitchestotheONposition.
Donotchangeanydipswitchesonanyofthe
SLAVEunits.
HotOut
ColdIn
GasIn
CAUTION