Owner manual

17
Product Technical Specifications
Tables 9a, 9b, 10a, and 10b list the major technical specifications for the MotorGuard product line.
Table 9a MotorGuard Technical Specifications Industrial
Current ratings Continuous current: 8 to 750 amps. See Rating and Dimension tables
Intermittent current: 150% for 1 minute out of every 60 minutes
VFD Drive output voltage 460/480 and 575/600 V, 3 ph, at fundamental base frequency
VFD Drive output
frequency
0 to 80 Hz
VFD Drive carrier
frequency
2 kHz and 12 kHz, ideally 4 kHz to 8 kHz
Control power input For fan operation.
Filter performance Maximum peak voltage of output waveform 480 V models: 1000 V
600 V models: 1500 V
Maximum dv/dt of output waveform 480 V models: 500 V/μs
600 V models: 1500 V/μs
Maximum elevation 3,000 feet (1,000 meters) as standard. Product must be equipped with
special cooling provisions for operation above this level
Maximum ambient
operating temperature
40 °C (104 °F) as standard. Product must be equipped with special
cooling provisions for operation above this temperature.
Maximum ambient storage
temperature
50 °C (122 °F)
Maximum humidity,
operating or storage
95%, non-condensing.
Enclosure options Open panel for mounting in an enclosure furnished by others
NEMA 1 enclosure
Enclosure finish Free standing enclosures: ANSI 61 gray
Wall mount enclosures: White Matte (beige) Munsel 5.8Y7.83/1
Agency approvals or
certifications
UL and cUL Listed to UL508A and CSA-C22.2 No. 14
Insertion impedance Approximately 6.5% at 60 Hz & full load current
Fusing and protection: Unit has internal fuse protection and a performance monitoring
circuit.
Capacitors Oil filled high endurance design (no PCBs)
Table 9b Only with Board Option
Status indication LEDs Green LED indicates: "Control Power ON"
Yellow LED indicates: "Normal Operation" (not faulted)
Fault relay De-energized when a fault is detected.
Form C contact for customer use.
Rated 0.6 A at 125 VAC and 110 VDC, 2 A at 30 VDC.