Owner manual

22
Table 11 Motor Power Terminal Wire Size Capacity Range and Tightening Torque (Cu or
Al) - Industrial
KMG IND
Model Numbers
Ground Lug
Input and Output
Motor Power
Wire Size
Torque
(in.-lb.)
Wire Size
Torque
(in.-lb.)
KMG8A to KMG55A
KMG8C to KMG45C
14 - 1/0 AWG 200 22 - 16 AWG
14 - 6 AWG
4 - 2 AWG and
1 AWG (7 & 19 strand only)
25
30
35
KMG65A to KMG130A
KMG55C to KMG130C
6 - 2/0 AWG 120 6 - 2/0 AWG 120
KMG160A to KMG200A
KMG160C to KMG200C
6 AWG - 250 MCM 275 6 AWG - 250 MCM 275
KMG250A to KMG305A
KMG250C to KMG305C
4 AWG - 600 MCM or
(2) 1/0 AWG - 250 MCM
500
4 AWG - 600 MCM or
(2) 1/0 AWG - 250 MCM
500
KMG362A
KMG362C to KMG420C
(2) 4 AWG - 350 MCM
275
(2) 4 AWG - 350 MCM
275
KMG420A to KMG600A
KMG500C to KMG600C
(2) 2 AWG - 600 MCM
500
(2) 2 AWG - 600 MCM
500
KMG750A
(3) 2 AWG - 600 MCM
375
(3) 2 AWG - 600 MCM
375
Table 11b Motor Power Terminal Wire Size Capacity Range and Tightening Torque (Cu or
Al) General Purpose
KMG GP
Model Numbers
Ground Lug
Input and Output
Motor Power
Wire Size
Torque
(in.-lb.)
Wire Size
Torque
(in.-lb.)
KMG55A
KMG45C
14 - 1/0 AWG
200
22 - 16 AWG
14 - 6 AWG
4 - 2 AWG and
1 AWG (7 & 19 strand only)
25
30
35
KMG65A to KMG130A
KMG55C to KMG130C
6 - 2/0 AWG
120
6 - 2/0 AWG
120
KMG160A to KMG200A
KMG160C to KMG200C
6 AWG - 250 MCM
275
6 AWG - 250 MCM
275
KMG250A to KMG305A
KMG250C to KMG305C
4 AWG - 600 MCM or
(2) 1/0 AWG - 250 MCM
500 4 AWG - 600 MCM or
(2) 1/0 AWG - 250 MCM
500
KMG362A
KMG362C to KMG420C
(2) 4 AWG - 350 MCM 275 (2) 4 AWG - 350 MCM 275
KMG420A to KMG600A
KMG500C to KMG600C
(2) 2 AWG - 600 MCM
500
(2) 2 AWG - 600 MCM
500
Connection Diagram
Figure 4 shows the typical wiring connections between the MotorGuard and the VFD and motor. Note
that separate conduits may be required for the control power and fault contact wiring. Refer to the
instructions for the VFD or other equipment to which the fault contact is connected.