Indoor Fireplace User Manual

31
41DVN / DVSN Direct Vent Gas Fireplace
20009999
System Checks (continued)
Defective thermo-generator. After the pilot has been lit for approximately three minutes,
(Millivolt system) and only the thermo-generator wire connected to the main
operator head, measure the voltage across TPTH and TP.
This open circuit voltage should be between 500mV and
750mV. Turn the pilot adjustment screw until the mV reading
falls within these parameters. (Counter-clockwise increases
mV reading, clockwise decreases)
Defective safety magnet. Verify operation of safety magnet in the following
(mV Plus systems) manner.
(A) Depress and hold pilot button.
(B) Verify open-circuit thermocouple voltage as de-
scribed in previous step.
(C) Reconnect thermocouple to valve.
(D) Measure the Millivoltage between the solder button
on the base of the safety magnet, and the valve
body. If the mV reading is above 6mV for vented
appliances, or 8.5 mV for un-vented appliances, and
the safety magnet does not hold, replace the valve.
(E) If closed circuit mV reading is the same as the open
circuit reading, the coil is electrically open. Replace
the valve.
Defective Safety Magnet Verify operation of safety magnet in the following
(Millivolt system) manner.
(A) Remove all wires from the terminals of the main
operator.
(B) Measure the electrical voltage between the terminals TPTH
and TP. If the voltage is above 110mV and the safety magnet
does not hold, replace the valve.
Pilot orifice blocked. Replace orifice with a new orifice of the exact size and
type.
Pilot drops out. Wrong pilot orifice. Replace the orifice with a new orifice supplied specifically for
the appliance and gas type in question.
No gas to main burner Low gas pressure to appliance. With the main burner functioning, adjust the inlet pressure
regulator to supply gas to the appliance within the design
parameters of the appliance manufacturer.
(Typically 7”NG, 11”LPG).
Pilot not lit. Light pilot and wait for thermo-generator to heat up
sufficiently to power the main operator. If pilot fails to
light, or hold, refer to above sections.
Control knob not in ON Rotate OFF/PILOT/ON control knob to the ON position.
position.
Thermostat/wall switch Thermostat not in ON position. Turn thermostat ON, and adjust temperature control to
will not cycle main call for heat.
burner.
Problem Possible Cause Solution