OSIRIA secondary clocks OSIRIA secondary clocks OSIRIA 220 AR KNX OSIRIA 230 AR KNX OSIRIA 230 SR KNX OSIRIA 240 AR KNX OSIRIA 240 SR KNX OSIRIA 241 AR KNX OSIRIA 241 BR KNX OSIRIA 242 AR KNX OSIRIA 242 SR KNX OSIRIA 251 BQ KNX OSIRIA 232 BQ KNX Updated: Jan-14 (Subject to change) 5009200 5009210 5009211 5009230 5009231 5009240 5009241 5009250 5009251 5009252 5009233 Page 1 of 15
OSIRIA secondary clocks Contents 1 FUNCTIONAL CHARACTERISTICS ......................................................................... 3 2 APPLICATION OPTIONS ............................................................................................. 3 3 TECHNICAL DATA ....................................................................................................... 3 4 OPERATION .................................................................................................................
OSIRIA secondary clocks 1 Functional characteristics With the Theben OSIRIA secondary clocks, a secondary clock system can be set up using the cable network of a KNX system. According to the particular version, they can display time or time and date The clocks are synchronised via time messages from the KNX bus.
OSIRIA secondary clocks 5 The "Secondary clock control" application program" 5.1 Selection in the product database Manufacturer Product family Product type Programname Theben AG Display units Time display OSIRIA KNX The ETS database can be found on our website: www.theben.
OSIRIA secondary clocks 5.2 Communication Objects Table 2 No. Object name Function 0 Receive time Receive time message 1 Receive date Receive date message 2 Automatic synchronization* Receive auto synch.
OSIRIA secondary clocks 5.2.1 Description of objects Object 0 "Receive time" Receives the time messages from the bus clock, e.g. TR 648 top2 RC KNX (order no. 6489212) to set the clock. Object 1 "Receive date" Receives the date messages from the bus clock, e.g. TR 648 top2 RC KNX (order no. 6489212). Object 2 "Automatic synchronisation" A 1 on this object starts the following process: The clock stops (second hand stops) The hands are reset to zero after approx.
OSIRIA secondary clocks 5.3 Parameters 5.3.1 Parameter pages Table 2 Function General Safety Description Type of clock Time query and alarm 5.3.
OSIRIA secondary clocks 6 Typical applications These typical applications are designed to aid planning and are not to be considered as an exhaustive list. It can be extended and updated as required. 6.1 Simple control of a clock system A system, consisting of several OSIRIA secondary clocks is controlled by a TR 648 top2 time switch. 6.1.1 Devices: TR 648 top2 RC KNX Various OSIRIA secondary clocks 6.1.
OSIRIA secondary clocks 6.1.3 Objects and links Table 1: No. TR648 top2 RC KNX Object name No. (all) OSIRIA clocks Object name 0 Local time 0 Receive time 1 Time query 1 Send time query Comment The TR 648 top2 sends the time to all OSIRIA secondary clocks via a common group address All secondary clocks send the time query to the TR 648 top2 via a common group address 6.1.4 Important parameter settings Standard or customer-defined parameter settings apply for unlisted parameters.
OSIRIA secondary clocks 6.2 Clock system with manual time synchronisation. A system, consisting of several OSIRIA secondary clocks is controlled by a TR 648 top2 time switch. 6.2.1 Devices: TR 648 top2 RC KNX (order no. 6489212) TA 2 KNX (order no. 4969202) Various OSIRIA secondary clocks 6.2.
OSIRIA secondary clocks 6.2.3 Objects and links Table 4: TR648 top2 OSIRIA No. TR648 top2 RC KNX Object name No. (all) OSIRIA clocks Object name 0 Local time 0 Receive time 1 Time query 1 Send time query No. (all) OSIRIA clocks Object name Comment Automatic synchronisation An ON telegram is sent to all clocks at the press of a button. The system auto synchronisation is triggered (see attachment).
OSIRIA secondary clocks 6.2.4 Important parameter settings Standard or customer-defined parameter settings apply for unlisted parameters.
OSIRIA secondary clocks 7 APPENDIX 7.1 Hand reset to zero When setting the hand to zero, the hour and minute hands are moved to a set position (12:00). This makes it possible to ensure the exact positioning of the hands during normal operation. The hand is reset to zero: After receiving a 1 on the Force synchonisation object. After first receipt of a time after restoration of bus voltage. 7.2 Synchronisation behaviour of clock The control unit must have received at least one time telegram to set the clock.
OSIRIA secondary clocks 8 Operating manual Updated: Jan-14 (Subject to change) Page 14 of 15