STE-8001 and STE-8201 sensors Installation Guide 7O 12O2 Set Point Section 1 Introduction to STE-8000 sensors Specifications ...........................................................................................................................4 Safety considerations .............................................................................................................6 Section 2 Installing STE-8000 sensors Planning for motion sensing ............................................................
KMC Controls Important notices ©2012, KMC Controls, Inc. WinControl XL Plus, NetSensor, and the KMC logo are registered trademarks of KMC Controls, Inc. BACstage and TotalControl are trademarks of KMC Controls, Inc. All rights reserved. No part of this publication may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language in any form by any means without the written permission of KMC Controls, Inc. Printed in U.S.A.
SECTION 1 Introduction to STE-8000 sensors This section provides a description of the KMC Controls STE-8001 and STE-8201 wall sensors. It also introduces safety information. Review this material before installing or operating the sensors. Models STE-8001 and STE-8201 are wall-mounted, temperature sensor for use with KMC BAC-8000 series VAV controllers.
Introduction to STE-8000 sensors Specifications KMC Controls Specifications Display Multifunctional LCD 1.88 x 1.25 in. (48 x 32 mm) Compatibility BAC-8000 series VAV controllers Controller Connection Connector type Cable type and length Eight-wire RJ-45 modular jack Standard Ethernet cable up to 75 feet (22.9 meters) Power Supplied by connected controller Mounting Surface mount directly to any flat surface or to a 2 x 4 inch or 4 x 4 inch handy-box.
STE-8001 and STE-8201 sensors Introduction to STE-8000 sensors Specifications Motion sensor range Detector type Range Model STE-8201 only Passive infrared 33 feet (10 meters). See diagrams X 10 m 32.8 ft Y 10 m 32.8 ft 46.5° 0° 0° 55° 10 m 32.8 ft 10 m 32.8 ft Side view Top view Dimensions A 7O 12O2 C B D F E Revision A A B C D E F 3.25 in. 5.16 in. 2.58 in. 3.25 in. 0.87 in. 1.07 in.
Introduction to STE-8000 sensors Safety considerations KMC Controls Models Temperature sensor only STE-8001 Temperature and motion STE-8201 Safety considerations KMC Controls assumes the responsibility for providing you a safe product and safety guidelines during its use. Safety means protection to all individuals who install, operate, and service the equipment as well as protection of the equipment itself. To promote safety, we use hazard alert labeling in this manual.
SECTION 2 Installing STE-8000 sensors This section provides important instructions and guidelines for installing the STE-8000 series sensors. Carefully review this information before installing the controllers. Installing the sensors includes the following topics that are covered in this section.
Installing STE-8000 sensors Rough-in preparation KMC Controls False detections may be triggered by: ◆ ◆ ◆ Rough-in preparation The temperature inside the detection range suddenly changes because of the entry of cold or warm air from an air-conditioning or heating unit. The sensor being directly exposed to sunlight, an incandescent light, or other source of far-infrared rays. Small animal movement. Complete rough-in wiring at each sensor location prior to sensor installation.
STE-8001 and STE-8201 sensors Installing STE-8000 sensors Maintenance 4. Insert the Ethernet cable coming from the base into the sensor. 5. Place the top of the sensor over the top of the mounting base and swing it down over the Allen screw brackets. Be careful not to pinch any wiring. 6. Back the Allen screws out of the brackets until they engage the sensor cover and hold it in place. Maintenance Revision A Remove dust as necessary from holes in top and bottom.
Installing STE-8000 sensors Maintenance 10 KMC Controls Revision A
SECTION 3 User functions This section covers topics for the end user in a facility. User functions are limited to changing the occupied temperature setpoints from the STE-8000. Operating the STE-8000 The functions are accessible through an STE-8000 series sensor. The functions are entered or changed using the buttons and display on the front of the STE-8000. ◆ ◆ Pressing either the up button or down button changes a selection, setting, or value. Pressing the setpoint button saves the setting or value.
User functions Changing setpoints Changing setpoints KMC Controls To enter or change the occupied setpoints you will need a Level 1 password. Enter occupied setpoints Procedure Steps STE display Starting display Start from the temperature display. 72 12S1 Enter the level one password 1. Press the button. 2. Press the or buttons to change the first digit. 3. Press the button to select the next digit. Repeat for all four digits. 4.
SECTION 4 Commissioning functions This topics in this section are advanced topics for control technicians and engineers. The commissioning functions that are accessible through an STE-8000 series sensor are values and settings that are entered during the installation and commissioning of a VAV terminal unit. Typically these functions do not change after the installation and commissioning process.
Commissioning functions The commissioning sequence The commissioning sequence KMC Controls Set the commission functions in the following sequence. 1. 2. 3. 4. 5. 6. Enter the commissioning mode Enter the commissioning mode on page 14 Setting up network communications on page 15 Box options on page 16 Setting commissioning setpoints on page 20 Setting the airflow setpoints on page 23 Balancing airflow on page 27 For access to the commissioning functions you will need a Level 2 password.
STE-8001 and STE-8201 sensors Setting up network communications Commissioning functions Setting up network communications Set the network communication settings before placing a controller on the network. Setting network settings requires entering the Level 2 password which is described in the topic Enter the commissioning mode on page 14. Procedure to set up network communications Procedure Starting display Steps STE display 1. Start at the temperature display. 2. Enter the Level 2 password.
Commissioning functions Box options Box options KMC Controls The box options set up the controller for the specific mechanical installation of the VAV terminal unit. Setting the box options requires entering the Level 2 password which is described in the topic Enter the commissioning mode on page 14. Procedure to set the box functions Procedure Starting display Steps STE display 1. Start at the temperature display. 2. Enter the Level 2 password. The display changes to the COMM.
STE-8001 and STE-8201 sensors Commissioning functions Box options Procedure to set the box functions (Continued) Procedure Set the mode of reheat for the terminal unit Steps STE display 1. Press the or buttons to choose one of the following reheat options. None—Reheat is not enabled. Staged—Enables two or three stage reheat. If lighting is enabled the staged reheat is set to two stages. If lighting is not enabled, three reheat stages are available.
Commissioning functions Box options KMC Controls Procedure to set the box functions (Continued) Procedure Set the damper direction to close Steps STE display 1. Press the or buttons to which direction to damper moves to close. CCW—The actuator turns counterclockwise to close the damper. DDIR CCW CW—The actuator turns clockwise to close the damper. 2. Press the button to save the damper option and advance to the next function. Set Point Set the dual duct mode 1.
STE-8001 and STE-8201 sensors Commissioning functions Box options Procedure to set the box functions (Continued) Procedure Advance or exit Steps STE display 1. Press the or buttons to select one of the following: • STPT, FLOW, or ADVC options • BACK to choose another commissioning function • EXIT to return to the temperature display. 2. Press the button to select the next function.
Commissioning functions Setting commissioning setpoints Setting commissioning setpoints KMC Controls The commissioning setpoints set the operational parameters and limits for the VAV terminal unit. Setting configuration setpoints requires entering a Level 2 password which is described in the topic Enter the commissioning mode on page 14. Procedure to set the commissioning setpoints Procedure Steps STE display Starting display Enter the Level 2 password. The display changes to the COMM.
STE-8001 and STE-8201 sensors Commissioning functions Setting commissioning setpoints Procedure to set the commissioning setpoints (Continued) Procedure Set the occupied cooling setpoint Steps STE display 1. Press the or buttons to set the occupied cooling setpoint. The setpoint will change in 0.5° increments. 2. Press the button to save the setpoint and advance to the next function. Set Point OCCL 74O Note: This setpoint can also be changed as described in the section User functions on page 11.
Commissioning functions Setting commissioning setpoints KMC Controls Procedure to set the commissioning setpoints (Continued) Procedure Steps STE display Set the minimum temperature differential setpoint 1. Press the or buttons to set the differential setpoint. The setpoint will change in 1° increments. 2. Press the button to save the setpoint and advance to the next function. Set the standby differential setpoint 1. Press the or buttons to set the standby differential setpoint.
STE-8001 and STE-8201 sensors Setting the airflow setpoints Commissioning functions Setting the airflow setpoints The airflow setpoints configure the airflow limits for the VAV terminal unit. Setting the airflow setpoints requires entering a Level 2 password which is described in the topic Enter the commissioning mode on page 14. Note If the VAV unit is a heat only or cooling only unit, the airflow setpoints for the unused mode must be set within the range of the mode in use.
Commissioning functions Setting the airflow setpoints KMC Controls Procedure to set the airflow setpoints (Continued) Procedure Set the cooling minimum airflow limit Steps STE display 1. Press the or buttons to set the minimum limit for cooling airflow. The setpoint will change in 1 CFM increments. 2. Press the button to save the setpoint and advance to the next function. Set Point Set the cooling maximum airflow limit 1. Press the or buttons to set the maximum limit for cooling airflow.
STE-8001 and STE-8201 sensors Commissioning functions Setting the airflow setpoints Procedure to set the airflow setpoints (Continued) Procedure Set the cooling minimum airflow limit Steps STE display 1. Press the or buttons to set the minimum limit for cooling airflow. The setpoint will change in 1 CFM increments. 2. Press the button to save the setpoint and advance to the next function. Set Point Set the cooling maximum airflow limit 1.
Commissioning functions Setting the airflow setpoints KMC Controls Procedure to set the airflow setpoints (Continued) Procedure Set the minimum limit for indoor air quality ventilation Steps STE display 1. Press the or buttons to set the minimum limit for ventilation airflow. The setpoint will change in 1 CFM increments. 2. Press the button to save the setpoint and advance to the next function. Set Point Set the maximum limit for indoor air quality ventilation 1.
STE-8001 and STE-8201 sensors Balancing airflow Commissioning functions Balancing airflow The airflow balancing method described in this section requires a flow hood or other accurate method to measure airflow. The airflow balancing procedure requires entering the Level 2 password which is described in the topic Enter the commissioning mode on page 14. Note If the VAV unit is a heat only or cooling only unit, the airflow setpoints for the unused mode must be set within the range of the mode in use.
Commissioning functions Balancing airflow KMC Controls The airflow balancing procedure (Continued) Procedure Measure and enter the actual maximum primary airflow Steps STE display The display begins flashing PMAX and also displays the actual airflow at the bottom. Note: The airflow will attempt to stabilize on the highest value for either the cooling or heating maximum airflow even if only one mode is operational.
STE-8001 and STE-8201 sensors Commissioning functions Balancing airflow The airflow balancing procedure (Continued) Procedure Advance or exit Steps STE display 1. Press the or buttons to select one of the following: • SEC to balance the secondary VAV for dual duct systems • BACK to choose another commissioning function • EXIT to return to the temperature display. 2. Press the button to select the next function.
Commissioning functions Balancing airflow KMC Controls The airflow balancing procedure (Continued) Procedure Measure and enter the actual minimum secondary airflow Steps STE display The display begins flashing SMIN and also displays the actual airflow at the bottom. Note: The airflow displayed by the STE-8000 in this step is the actual, uncorrected airflow. SMIN OO 1. Wait for the minimum airflow value to stabilize. 2. With a flow hood, measure the actual airflow. 3.
STE-8001 and STE-8201 sensors Advanced options Commissioning functions Advanced options The advanced options set up passwords and special features in the controller. Setting the advance options requires entering the Level 2 password which is described in the topic Enter the commissioning mode on page 14. Procedure to set the advanced options Procedure Starting display Steps STE display 1. Start at the temperature display. 2. Enter the Level 2 password. The display changes to the COMM.
Commissioning functions Advanced options KMC Controls Procedure to set the advanced options (Continued) Procedure Steps STE display Enter a new Level 2 password password Note: Entering four zeros (0000) removes the password. 1. Press the or buttons to change the first digit. 2. Press the button to select the next digit. Repeat for all four digits. 3. When the button is pressed for the last digit, the new password is saved and the display advances.
STE-8001 and STE-8201 sensors Commissioning functions Advanced options Procedure to set the advanced options (Continued) Procedure Advance or exit Steps STE display 1. Press the or buttons to select one of the following: • STPT, FLOW, or BOX options • BACK to choose another commissioning function • EXIT to return to the temperature display. Press the button to select the next function.
Commissioning functions Advanced options 34 KMC Controls Revision A