Multiprotocol Ethernet Interface User's Manual

70
ICC
12) Apply the settings using the “Set” button.
13) You should now be able to confirm that the 1756-ENET/B module is
configured properly by (for example) opening the module’s web interface in
a web browser.
13.2.4 ControlLogix Example: I/O Messaging
This section will demonstrate how to setup and use an EtherNet/IP I/O
connection via vendor-specific assembly instances 100 & 150. EtherNet/IP I/O
messaging allows the drive’s registers to be directly mapped into tags in the
ControlLogix PLC. Once an I/O connection is established, it is automatically
synchronized at an interval defined by the Requested Packet Interval (RPI).
1) Switch to offline mode.
2) Right click on the 1756-ENET/B node under the I/O Configuration in the
controller organizer view and choose “New Module…”
3) Choose “Generic Ethernet Module” in the Select Module dialog box and
click “OK”. Refer to Figure 66.
Figure 66: Adding a New Generic Ethernet Module
4) The module properties dialog box will open (refer to Figure 67). Enter a
Name and Description which will allow easy identification of the drive on
the network (the tags created in RSLogix 5000 will be derived from this
Name). Because all drive data is stored as 16-bit registers, change the
“Comm Format” selection to “Data-INT”. Enter the IP address of the
targeted interface card.