prestige Control Application Supplement - TriMax LI STED WARNING This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions within this document and within the PRESTIGE Boiler Installation and Maintenance Manual before proceeding. It is recommended to follow the procedures in the steps given. Skipping or missing procedural steps could result in severe personal injury, death or substantial property damage.
Table of Contents Product and Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Operating Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Entering Installer Access Code. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Trimax Installer Menu Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 CH Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Product and Safety Information IMPoRTanT InfoRMaTIon - REad BEfoRE PRocEEdInG WARNING This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions within this document and within the PRESTIGE Boiler Installation and Maintenance Manual before proceeding. It is recommended to follow the procedures in the steps given.
operating Information oPERaTInG InfoRMaTIon The TriMax Boiler Management System is designed to be flexible yet easy to use. TriMax monitors and controls the Prestige to operate as efficiently as possible. TriMax monitors the boiler supply, return and flue gas temperatures and operates the igniter, gas valve and blower. TriMax uses this information to modulate the boiler’s firing rate to maintain the required setpoint.
Entering Installer access code EnTERInG InSTaLLER accESS codE The InSTaLLER button (the small round button) provides the installing contractor with full access to all available features after entering an access code. Installer Button fig. 1: TriMax navigation Buttons Entering installer access code procedure 1. Press the round InSTaLLER button. 2. Enter the installer access code “054” by using the LEfT and RIGHT buttons to select a digit and the UP and doWn buttons to change the digit.
Trimax Installer Menu Structure TriMax Installer Menu Structure Home Screen Installer Access Code ENTER INSTALLER ACCESS CODE 05[4] Installer Menu CH & DHW Settings CH & DHW Settings Menu CH Settings Reset All Settings Cascade Menu Reset All Settings Cascade Information Manual Operation Manual Operation FAN Press OK button to restore factory settings, any other button to keep current settings CH CH1 DHW SYS CH2 4 Released Off Off Off
cH Settings Heating Settings cH Settings navigation: Home Screen>Installer Menu>cH & dHW Settings>cH Settings The CH Settings menu contains settings related to central heating operation. Each line contains a CH Setting followed by its current value. Six CH Settings are displayed on the screen at one time. Press the UP or doWn buttons to scroll through additional CH Settings. Heating operation default: Enabled Heating Operation allows the central heating function to be enabled and disabled.
cH Settings absolute Max cH Setpoint default: 194°f [90°c] Absolute Max CH Setpoint limits the setpoint during a central heating call. This setting can be used to prevent a user from adjusting the central heating setpoint or outdoor reset curve above a safe operating temperature in the EZ Setup Menu. A warning screen will be displayed in EZ Setup if the user attempts to raise the setpoint above the Absolute Max CH Setpoint.
cH Settings Reset curve Warmest day default: 64°f [18°c] Reset Curve Warmest Day is the warmest outdoor design temperature of the heating system when an Outdoor Reset option is chosen in CH Demand. This setting is not applicable when a Setpoint option is chosen in CH Demand. Press the LEfT or RIGHT buttons to adjust the Reset Curve Warmest Day then press the oK button to store the setting.
cH Settings Pump constant circulation default: disabled Pump Constant Circulation allows the central heating circulators to be constantly enabled even without a central heating call. A domestic hot water call will cause the circulators to be disabled during the domestic call as long as DHW Priority is enabled. Press the UP or doWn buttons to select Enabled or Disabled then press the oK button to store the setting.
cH Settings WARNING freeze Protection should only be disabled when the system contains antifreeze to prevent the system from freezing. Serious damage could occur to the Prestige as well as the entire heating system if freeze Protection is disabled without antifreeze in the system. WARNING The Prestige should nEVER be installed in a location where freezing could occur. Subjecting the Prestige to freezing conditions could lead to freezing of the condensate possibly causing serious injury or death.
cH Settings System Pump default: cH1/cH2 System Pump allows the system pump operation to be adjusted for the application. Press the UP or doWn buttons to select the desired System Pump operation then press the oK button to store the setting. The System Pump options are: • cH1/cH2/dHW – The system pump will be enabled for any CH1, CH2, or DHW call. Figure 2, page 11 illustrates a typical existing system requiring this setting.
cH Settings fig.
cH Settings fig.
cH Settings fig.
dHW Settings dHW Settings DHW Settings navigation: Home Screen>Installer Menu>cH & dHW Settings>dHW Settings The DHW Settings menu contains settings related to domestic hot water operation. Each line contains a DHW Setting followed by its current value. Six DHW Settings are displayed on the screen at one time. Press the UP or doWn buttons to scroll through additional DHW Settings. dHW operation default: Enabled DHW Operation allows the domestic hot water function to be enabled and disabled.
dHW Settings demand Type PRESTIGE Solo default: Switch PRESTIGE Excellence default: Sensor Demand Type allows the installer to select the type of device which will generate a domestic hot water call. Press the UP or doWn buttons to select the DHW Demand Type then press the oK button to store the setting.
dHW Settings DANGER The dHW on differential setting greatly affects the production of domestic hot water. a low setting could result in a rapid response to a domestic hot water call resulting in a potential scald hazard. It is strongly recommended that the installer utilize a thermostatic mixing valve on the hot water outlet of the Indirect Water Heater. failure to comply could result in severe personal injury, death, or substantial property damage.
dHW Settings DHW Priority dHW Priority default: Enabled DHW Priority allows the domestic hot water priority function to be enabled and disabled. Press the UP or doWn buttons to select Enabled or Disabled then press the oK button to store the setting. • Enabled- Domestic hot water calls will have priority over a central heating call. The boiler setpoint will be set to the domestic hot water setpoint during a domestic hot water call.
dHW Settings dHW To cH call Blocking default: 1 Minute DHW To CH Call Blocking sets the minimum time between a DHW burner firing and a CH burner firing. At the completion of a DHW burner firing, the DHW to CH Call Blocking time will begin. The burner will not fire again for a central heating call until after the DHW To CH Call Blocking time has elapsed. The DHW To CH Call Blocking time only prevents the burner from firing, the central heating circulators will respond to a central heating call.
Reset all Settings Reset all Settings navigation: Home Screen>Installer Menu>Reset all Settings Reset All Settings allows the installer to reset all CH, DHW, and Cascade settings back to the original PRESTIGE Solo factory defaults. Follow the onscreen instructions to reset all settings back to the original factory defaults NOTICE PRESTIGE Excellence units require setting Prestige Model to Excellence and dHW demand Type to Sensor after using the Reset all Settings function.
factory Trimax Settings factory Trimax Settings Heating Setting Heating operation demand factory default Minimum Setting Maximum Setting EZ Setup Reset Installer Reset Enabled Switch & Setpoint absolute Max cH Setpoint 194°f [90°c] 68°f [20°c] 194°f [90°c] cH1 Maximum Setpoint 180°f [82°c] 68°f [20°c] 194°f [90°c] cH1 Minimum Setpoint 120°f [49°c] 60°f [15°c] 140°f [60°c] Reset curve coldest day 0°f [-18°c] -30°f [-34°c] 50°f [10°c] Reset curve Warmest day 64°f [18°c] 60°f [15°c] 78°
cascade operating Information cascade operating Information The TriMax Boiler Management System includes a Cascade function which allows multiple Prestige boilers to operate together without the need for an external controller. One Prestige will be selected as the Master and will be wired to accept all the low voltage control signals. The other Prestige boilers will be designated as Slaves and will only have a communication cable connecting them to the other boilers in the Cascade System.
Trimax cascade Menu Structure Trimax cascade Menu Structure Installer Menu Cascade Cascade Menu Cascade Cascade Information Menu Cascade Information Cascade Role System Temp.
cascade Installation cascade Installation – System Piping Standard Cascade installations will utilize a balanced manifold system as the primary / secondary connection to the system piping as shown in Figure 6, page 26 or a reverse return piping arrangement as shown in Figure 8, page 28. Split Cascade installations will utilize a balanced manifold system as the primary / secondary connection to the central heating loop.
cascade Installation cascade Installation – cascade communication cable • A communication cable PTCAB01 must be installed between each boiler in the Cascade System. The cable has a 6 pin molex connector on one end and bare wires on the other end. The molex connector plugs into the Cascade Slave connector of the Slave boiler. The bare wires terminate on the Cascade Master terminals of the Master boiler or prior Slave boiler in cascades of three or more boilers.
cascade Installation • Power Supply – A dedicated 120 VAC / 15A minimum service must be used to power the boilers in the Cascade System. Multiple boilers in the Cascade System can be placed on the same electrical circuit. Each boiler can draw a maximum of 8 amps. • Alarm Wiring – The alarm contact closes whenever that particular Prestige is in a soft or hard lockout. The alarm contact will also close on the Master boiler when any of the Slave boilers are locked out.
note: Reference Fig. 7, page 27 for cascade wiring. cascade Installation fig.
cascade Installation note: Reference Fig. 6, page 26 for cascade piping. fig.
note: Reference Fig. 9, page 29 for cascade wiring. cascade Installation fig.
cascade Installation note: Reference Fig. 8, page 28 for cascade piping. fig.
fig. 10: Split cascade System 30 note 2: DHW Priority must be set to Enabled in DHW Settings of the Cascade Master for proper operation. note 1: Reference Fig. 11, page 31 for cascade wiring.
cascade Installation note: Reference Fig. 10, page 30 for cascade piping. fig.
cascade Information cascade Information Cascade Information navigation: Home Screen>Installer Menu>cascade>cascade Information Cascade Role Master Cascade Information provides real time operating information of the System Temp. 86ºF Cascade System. Each line contains an information item followed by its Active Boilers 0 current value. See below for a list of all Cascade Information items.
cascade Settings Cascade Setting cascade Settings navigation: Home Screen>Installer Menu>cascade>cascade Settings The Cascade Settings menu contains settings related to cascade operation. Each line contains a Cascade Setting followed by its current value. Six Cascade Settings are displayed on the screen at one time. Press the UP or doWn buttons to scroll through additional Cascade Settings.
cascade Settings Boiler Enabling algorithm The Master boiler uses the following algorithm to determine when the next boiler can be enabled: Number of Boilers Firing +1 x Minimum Firing Rate = Individual Boiler Firing Rate Number of Boilers Firing Once the currently fired boilers reach the calculated firing rate, the next boiler can be enabled without affecting the overall cascade firing rate.
cascade Settings cH or dHW Boilers default: 0 The CH or DHW Boilers setting specifies how many boilers in a Split Cascade System will respond to a domestic hot water call. The CH or DHW Boilers always include the Master boiler. The remaining boilers will only respond to central heating calls. This allows the Cascade System to satisfy both central heating and domestic hot water calls at the same time.
cascade Settings NOTICE only make adjustments to this setting after consulting Triangle Tube Technical Support. Improper adjustment of cH Proportional Gain could lead to temperature fluctuations and erratic cascade operation. cH Integral Gain default: 245 CH Integral Gain allows the cascade response to be adjusted for a central heating call. CH Integral Gain has the greatest influence when the system temperature is close to the setpoint.
cascade Settings - • To reach the setpoint faster, increase the DHW Proportional Gain value by 2. Perform Cascade Autodetection and initiate a domestic hot water call. Observe the cascade response and make further adjustments if necessary. decrease dHW Proportional Gain - The Cascade System will take longer to reach the setpoint, but setpoint overshooting is minimized. - If the setpoint is reached too quickly, decrease the DHW Proportional Gain value by 2.
cascade Settings NOTICE only make adjustments to this setting after consulting Triangle Tube Technical Support. Improper adjustment of dHW Integral Gain could lead to temperature fluctuations and erratic cascade operation. Modbus address default:0=BcST Modbus Address assigns the boiler with a unique address in the Modbus control system. Press the LEfT or RIGHT buttons to change the Modbus Address then press the oK button to store the setting.
Modbus Interface Modbus Interface The Modbus Interface allows a Building Management System (BMS) to directly connect to the Prestige. A BMS can read information from the boiler to determine its operating state, lockout status, sensor readings, etc. A BMS can also operate the boiler by providing a setpoint.
Modbus Interface Table 9: Input Registers (Read only) Address DEC (HEX) 0 (0x0000) Supported Commands 0x04 Description Byte: Format Boiler Status LB: Flag8 Bit: Description 0: PC Manual Mode 1: DHW Mode 2: CH Mode 3: Freeze Protection Mode 4: Flame Present 5: CH(1) Pump 6: DHW Pump 7: System / CH2 Pump 0 = Off, 1 = On 1 (0x0001) 0x04 Lockout Status MB: Flag8 Bit: Description 1: Lockout Code Type 0 = Automatic Reset Lockout 1 = Manual Reset Lockout Notes LB:U8 Value = Lockout Code 0 = Single /
Manual operation Manual operation navigation: Home Screen>Installer Menu>Manual operation The Manual Operation Screen allows the burner and circulators to be manually enabled for testing. fan Press the oK button while the FAN icon is highlighted to manually fire the burner and power the CH (1) circulator. Press the LEfT and RIGHT buttons to adjust the firing rate from 0% (Low Fire) to 100% (High Fire). Hold down the LEfT or RIGHT buttons to rapidly increase or decrease the firing rate.
Additional quality water heating equipment available from Triangle Tube/Phase III MAXI-FLO AND SPA HEAT EXCHANGERS - Construction of high quality corrosion resistant stainless steel (AISI 316) or titanium - Specially designed built-in flow restrictor to assure maximum heat exchange - Compact and light weight - Available in 5 sizes that can accommodate any size pool or spa SMART INDIRECT FIRED WATER HEATERS - Exclusive tank-in-tank design - Stainless steel construction - Available in 8 sizes -