Installation Guide

52
Step 05 – T
est the connection of each
output
This step helps you to check if the output
terminals were connected correctly and
securely
. During the connection test, check
if your HV
AC equipment connected to the
respective output terminal is turned on.
1. Rotate the jog dial clockwise to turn on
t
he output as follows:
: Only W1 is on, all others off
: Only W2 is on, all others off
: Only G is on, all others off
: Only O/B is on, all others off
: Only ACC is on, all others off
After you rotate the jog dial, there may be a few
seconds delay before the HV
AC equipment
turns on.
This is not a malfunction.
2.
Press the jog dial to end the connection test.
A
ll the outputs will be turned off.
: All outputs off
: Only Y1 is on, all others off
: Only Y2 is on, all others off