Product Manual

INSTALLATION / OPERATION INSTRUCTIONS
TERMS:
Cut-out-Temperaturesensedbythe
controllerthatshutsthecompressor
off.
Cut-in-Temperaturesensedbythe
controllerthatturnsthecompressor
on.
REQUIRED TOOLS
•PhillipsHeadScrewdriver
•5/64"or2mmAllenWrench
•T-7TorxWrench
__________ STEP 1 ___________
Unplugthecooler.
__________ STEP 2 ___________
Removethescrewsthatsecure
thetemperaturecontroltothe
evaporatorfanhousinginthe
ceilingofthecabinet.Seeimageto
therightfortemperaturecontrol
location.
__________ STEP 3 ___________
Pulloutgentlyfromcabinet.
__________ STEP 4 ___________
Forhighelevationinstallations,it
maybenecessaryto"warm-up"the
setpoints.Tomaketheadjustment,
inserttheappropriatetoolineach
adjustmentscrewandturn1/4ofa
revolutionclockwise(totheright).
Thisprocedurewilladjustboth
thecut-inandcut-outabout2°F
warmer.
__________ STEP 5 ___________
Makesuretoreconnectthepink
wiretotheproperspade
terminalwhenreinstalling.
NOTE:
Mechanical temperature
controllers are affected when
functioning at high altitude. The
cut-in and cut-out temperatures will
be colder than when the controller
functions closer to sea level
Danfoss Temperature Control (High Altitude Adjustment Only!)
Cut-outAdjustmentScrewAllen(5/64"
or2mm)(clockwiseforwarmer)
Cut-inAdjustmentScrewTorx(T-7)
(clockwiseforwarmer)
CompressorConnection(pink)
CompressorConnection(pink)
TEMPERATURE CONTROL ADJUSTMENT FOR
HIGH ALTITUDE ONLY!
22
22
True Food Service Equipment, Inc.