Datasheet

Awaiting Image
UL1.3-6
Dimensions
F1 Terminal
UL 1.3-6
6V 1.3AH
General
Normal Voltage 6V
Normal Capacity (20HR) 1.3AH
Terminal Type Standard Terminal F1
Optional Terminal -
Container Material Standard Option ABS
Flame Retardant Option (FR) UL94:VO
Rated Capacity 1.3 AH/0.060A (20hr, 1.80V/cell, 25°C / 77°F)
1.20 AH/0.112A (10hr, 1.80V/cell, 25°C / 77°F)
1.02 AH/0.204A (5hr, 1.75V/cell, 25°C / 77°F)
0.918 AH/0.306A (3hr, 1.75V/cell, 25°C / 77°F)
0.754 AH/0.754A (1hr, 1.60V/cell, 25°C / 77°F)
Max Discharge Current 18A (5s)
Internal Resistance Approx 65mΩ
Discharge Characteristics Operating Temp. Range Discharge: -15 ~ 50°C (5 ~ 122°F)
Charge: 0 ~ 40°C (5 ~ 104°F)
Storage: -15 ~ 40°C (5 ~ 104°F)
Nominal Operating Temp. Range 25 ± 3°C (77 ± 5°F)
Cycle Use Initial Charging Current less than 0.36A.Voltage
Standby Use No limit on Initial Charging Current Voltage
Capacity affected by Temperature 40°C (104°F) 103%
25°C (77°F) 100%
0°C (32°F) 86%
Design Floating Life at 20°C 5 Years
Self Discharge Ultracell batteries may be stored for up to 6 months at 25°C(°77F) and then a refresh charge is required. For
higher temperatures the time interval will be shorter.
Part Number: UL1.3-6
Length: 97 ± 2 mm (3.82 inches)
Width: 24 ± 2 mm (0.94 inches)
Container Height: 51.5 ± 2 mm (2.03 inches)
Total Height
(with terminal): 57.5 ± 2 mm (2.26 inches)
Approx Weight: Approx 0.29kg (0.639lbs)
57.5 2
51.5 2
97 2
24 2
5. 5
3. 2 [ 0.12 6]
6.35 [0.2 5]
0. 8 [0 . 0 3 1] 4. 75 [0 . 1 87]
1
Ultracell (UK) Ltd | Vesty Business Park | Vesty Road | Liverpool | L30 1NY | United Kingdom
Tel: +44 (0) 151 523 2777 Fax: +44 (0) 151 523 0855 Email: info@ultracell.co.uk
www.ultracell.co.uk
ALL DATA IS SUBJECT TO CHANGE WITHOUT NOTICE