Installation Guide

ZURN WILKINS
1747 Commerce Way, Paso Robles, CA 93446 Phone:855-663-9876 Fax:805-238-5766
MODEL 350XL 3/4" & 1" (STANDARD & METRIC)
0
5
10
15
0 20 40 60 80
FLOW RATES (GPM)
PRESSURE LOSS (PSIG)
0
34
69
103
0.00 1.26 2.52 3.79 5.05
FLOW RATES (l/s)
PRESSURE LOSS (kpa)
IS350XL 34-1 (REV. 4/13)
4
Performance Characteristics
Troubleshooting
PROBLEM
1. LEAKING CHECK VALVES
2. LOW OR NO FLOW
POSSIBLE CAUSES
1. Debris on seat or seal ring
2. Damaged seat
3. Damaged seal ring
4. Damaged check o-ring
1. Device installed backwards
2. Shut-off valves or valve upstream
may not be fully open
3. Low supply pressure
CORRECTIVE ACTION
1. Clean seat and seal ring area
2. Replace seat
3. Replace poppet
4. Replace check o-ring
FLOW CHARACTERISTICS
3/4" (20mm)
1" (25mm)
SPECIFICATIONS
Maximum working water pressure 175 PSI
Maximum working water temperature 180°F
Hydrostatic test pressure 350 PSI
End connections Threaded ANSI B1.20.1
Capacity thru Schedule 40 Pipe
Pipe size 5 ft/sec 7.5 ft/sec 10 ft/sec 15 ft/sec
1/8" 1 1 2 3
1/4" 2 2 3 5
3/8" 3 4 6 9
1/2" 5 7 9 14
3/4" 8 12 17 25
1" 13 20 27 40
1 1/4" 23 35 47 70
1 1/2" 32 48 63 95
2" 52 78 105 167
Proper performance is dependent upon licensed, qualied personnel performing regular, periodic testing according to ZURN
WILKINS’
specications and prevailing governmental & industry standards and codes and upon following these installation in-
structions. Failure to do so releases ZURN WILKINS of any liability that it might otherwise have with respect to that device. Such
failure could also result in an improperly functioning device.
Proposition 65 Warning This product contains chemicals known to the State of California to cause cancer or birth defects
or other reproductive harm.
®
www.zurn.com