Datasheet

UniPi Axon S105
Communication
Ethernet 1× 1Gbit Ethernet
Serial channels 2× RS485, 1x RS232
1× 1-Wire
Comm. speed RS485 1 134 baud .. 115 kbaud
Comm. speed RS485 3 50 baud .. 3 Mbaud
Galvanic isolation RS485 Yes
Comm. speed RS232 50 baud .. 3 Mbaud
Galvanic isolation RS232 No
Galvanic isolation 1-Wire Yes
Digital inputs
Number of inputs × groups 4 × 1
Common connector DIGND
Galvanic isolation Yes
Functions of inputs Signalization, counter,
Direct Switch
Operation range 5 – 40 V DC
Input voltage of log. 0 Max. 3,5 V DC
Input voltage of log. 1 Min. 5 V DC
Input resistance of log. 1 6 200Ω
Delay 0–>1/1–>0 20 μs / 60 μs
Digital outputs
Number of outputs ×
groups
4 × 1
Common connector DOGND
Galvanic isolation No
Type of output Transistor
Aditional functions PWM
Switchable voltage 5 – 50 V DC
Switchable current
continual/pulse
750 mA / 1 A
Max. total current
DO1.1 – DO1.4
1A
Time to switch on/off Typ. 130 ns / 20ns
Switching speed Max. 200 kHz/8bit
Dimensions and weight
Dimensions 72 × 90 × 59 mm
Weight 172 g
Analog inputs
Number of inputs × groups 1 × 1
Common connector AGND
Available functions 0 – 10 V
0 – 20 mA
Galvanic isolation No
Resolution 12 bits
Conversion speed 10μs
Analog outputs
Number of outputs × groups 1 × 1
Common connector AGND
Available functions AO 0 – 10V / 0 – 20mA
Resistance measure:
0 – 2 kΩ, Ni1000, Pt1000
Galvanic isolation No
Resolution 12 bits
Range/current 10V/20mA
Conversion speed 1ms
Power supply
Rated voltage - SELV 24 V DC
Voltage tolerance –15% .. +25%
20,4 .. 30 V DC
Power consumption Typ. 3W
Max. 12W
Internal protection Yes
Installation and operating conditions
Operating temperature 0 °C .. + 55 °C
Storing temperature -25 °C .. +70 °C
Dielectrical strength In accordance with
EN 60950
Degree of protection IP (IEC
529)
IP20
Operation position Horizontal
Installation On 35mm DIN rail into
distribution box
Connection Pluggable terminal blocks
Wire gauge Max. 2,5 mm
2
Standards compliance
ČSN EN 6060730-1
ČSN EN 6095-1 ed. 2
ČSN EN 61000-6-3 ed. 2
ČSN EN 55014-1 ed. 3
ČSN EN 55022 ed. 3
2006/95/EC, 2004/108/ES, 2014/35/EU, 2014/30/EC