Use and Care Guide

-5-
FLOOR PROTECTOR
Your wood stove should be placed on a 1 inch, non-combustible surface with a
k factor of 0.84. For multiple layers, add R-values of each layer to determine the
overall R-value. The R value for the required board is 1.2. If there is a horizontal
section of chimney connector, the oor protector should go under it and 2 inches
beyond each side
Convert specication to R-value:
k-factor is given with a required thickness (T) in inches: R=1/k x T
C-factor is given: R=1/C
Example:
If the oor protector is 4” brick with a C-factor of 1.25 over 1/8” mineral
board with a “k” factor of 0.29 the total R-value of the system is:
4” brick C=1.25, R=1/1.25=0.8
1/8” mineral board K=0.29, R=1/0.29 x 0.125=0.431
Total R = Rbrick + Rmineral = 0.8 + 0.431 = 1.231
Total R is greater than 1.2, the system is acceptable.
The oor protector should exceed the stove as follows:
CLEARANCES TO COMBUSTIBLES
It is of utmost importance that the clearances to combustible materials be strictly adhered to during
installation of the stove. Refer to the tables below :
Floor to ceiling height must be at least 7’ (2.13m) in all cases.
Do not place any combustible material within 4’ (1.2m) of the front of the unit.
The clearance between the ue pipe and a wall are valid only for vertical walls and for vertical ue pipe.
The chimney connector must not pass through an attic or roof space, closet or similar concealed space, a
oor, or a ceiling.
For Canadian installations, where passage through a wall, or partition of combustible construction is
desired, the installation must conform to CAN/CSA-B365.
A ue pipe crossing a combustible wall must have a minimum clearance of 18” (457.2mm).
To reduce ue clearances from combustible materials, contact your local safety department.
Single Wall Pipe (Double Wall Pipe)
Model A B C D E F
2500
12
(305mm)
20
(508mm)
16
(406mm)
30
(762mm)
10.5
(267mm)
20
(508mm)
Front Sides Rear
26”
(660mm)
8”
(203mm)
¶6”
(152mm)
- Canadian installations require 8” (203mm)