COMBUSTIBLE WALL CHIMNEY CONNECTOR PASS-THROUGHS
Method A. 12” (304.8 mm) Clearance to Combustible Wall
Member: Using a minimum thickness 3.5” (89 mm) brick and a
5/8” (15.9 mm) minimum wall thickness clay liner, construct a
wall pass-through. The clay liner must conform to ASTM C315
(Standard Specication for Clay Fire Linings) or its equivalent.
Keep a minimum of 12” (304.8 mm) of brick masonry between
the clay liner and wall combustibles. The clay liner shall run
from the brick masonry outer surface to the inner surface of the
chimney ue liner but not past the inner surface. Firmly grout or
cement the clay liner in place to the chimney ue liner.
Method B. 9” (228.6 mm) Clearance to Combustible Wall
Member: Using a 6” (152.4 mm) inside diameter, listed, factory-
built Solid-Pak chimney section with insulation of 1” (25.4 mm) or
more, build a wall pass-through with a minimum 9” (228.6 mm)
air space between the outer wall of the chimney length and wall
combustibles. Use sheet metal supports fastened securely to wall
surfaces on all sides, to maintain the 9” (228.6 mm) air space.
When fastening supports to chimney length, do not penetrate
the chimney liner (the inside wall of the Solid-Pak chimney). The
inner end of the Solid-Pak chimney section shall be ush with the
inside of the masonry chimney ue, and sealed with a non-water
soluble refractory cement. Use this cement to also seal to the
brick masonry penetration.
Method C. 6” (152.4 mm) Clearance to Combustible Wall
Member: Starting with a minimum 24 gage (.024” [.61 mm])
6” (152.4 mm) metal chimney connector, and a minimum 24
gage ventilated wall thimble which has two air channels of 1”
(25.4 mm) each, construct a wall pass-through. There shall be a
minimum 6” (152.4) mm separation area containing berglass
insulation, from the outer surface of the wall thimble to wall
combustibles. Support the wall thimble, and cover its opening
with a 24-gage minimum sheet metal support. Maintain the 6”
(152.4 mm) space. There should also be a support sized to t
and hold the metal chimney connector. See that the supports
are fastened securely to wall surfaces on all sides. Make sure
fasteners used to secure the metal chimney connector do not
penetrate chimney ue liner.
Method D. 2” (50.8 mm) Clearance to Combustible Wall
Member: Start with a solid-pak listed factory built chimney
section at least 12” (304 mm) long, with insulation of 1” (25.4
mm) or more, and an inside diameter of 8” (2 inches [51 mm]
larger than the 6” [152.4 mm] chimney connector). Use this as a
pass-through for a minimum 24-gauge single wall steel chimney
connector. Keep solid-pak section concentric with and spaced
1” (25.4 mm) off the chimney connector by way of sheet metal
support plates at both ends of chimney section. Cover opening
with and support chimney section on both sides with 24 gage
minimum sheet metal supports. See that the supports are fastened securely to wall surfaces on all sides. Make
sure fasteners used to secure chimney ue line.
NOTES:
1. Connectors to a masonry chimney, excepting method B, shall extend in one continuous section through
the wall pass-through system and the chimney wall, to but not past the inner ue liner face.
2. A chimney connector shall not pass through an attic or roof space, closet or similar concealed space, or a
oor, or ceiling.