Installation Guide

Installation instructions
Textile care system
J14001113-R04
27/03/2015
2
Electrical connections
Electrical connections must be carried out by qualified personnel in accordance with the guidelines and
standards for low-voltage installations and the specifications of the local electricity supply companies.
A plug-in appliance may only be connected to a socket outlet with earthing contact, installed according to
specifications. An all-pole mains isolating device with 3 mm contact opening should be provided in the
house wiring system. Switches, plug and socket devices, circuit breakers and fusible cut-outs which are
accessible after installation and which have all-poles switching are permissible as isolating devices. Effect-
ive earthing and separately installed neutral and earth conductors ensure safe and fault-free operation.
After installation, live parts and cables with basic insulation must not be accessible. Check old installa-
tions.
The appliance is designed for use up to a max. altitude of 2000 m above sea level.
Refer to the identification plate for information on the required mains voltage, current type and fuse protection.
Do not cut off the plug.
Installation
Do not install the appliance behind a door that locks, a sliding door or a door with a hinge that lies opposite
the hinge of the appliance.
Free-standing position
When positioning a REFRESH-BUTLER so that it is free-standing, a distance of min. 3mm must be kept to
the walls to the left and right.
1960
≥ 3
775
570
≥11
≥ 50