Technical data

Installation and maintenance instructions ecoTEC exclusive 0020017768_0530
7.2 Overview of the settable installation parameters
The following parameters can be set to match the
appliance to the heating system and to suit the
customers requirements:
Display Meaning Adjustable parameters
Default
setting
Appliance-specific
setting
d.0 Heating partial load ecoTEC exclusive 832
ecoTEC exclusive 838
27 kW
30 kW
22 kW
27 kW
d.1 Pump overrun time for heating operation
(starts after completion of heat demand)
2 - 60 min 5 min
d.2 Max. blocking time heating at 20°C feed
temperature
2 - 60 min 20 min
d.14 Pump speed target value Target value internal pump in % - possible
settings: Auto, 53, 60, 70, 85, 100 %
Auto
d.17 Heating flow/return regulation changeover 0 = flow, 1 = return 0
d.18 Pump mode (return flow) 0 = return, 1 = nonstop, 2 = winter 0
d.26 Changeover option relay to electronic 1 = circulation pump
2 = Ext. pump (default)
3 = storage charging pump
4 = vapour extraction hood
5 = external throttle
6 = ext. fault signal (without maintenance
display)
2
d.71 Target value max. heating flow temperature 40 to 85 °C 75 °C
d.84 Maintenance indicator: Number of hours
until the next maintenance
0 to 3000h and „-“
(300 corresponds to 3000 h, „-“ = deactivated)
-
Table 7.1 Adjustable parameters
h
Note!
You can enter your settings in the end column
after setting the appliance-specific parameters.
Note!
The diagnosis points d.17, d.71 and d.84 are lo-
cated in the 2nd. diagnosis level, see Section
9.1.2
7.2.1 Setting the heating partial load
The units are set in the factory to a possible heat load
but not yet to the maximum value. Under diagnosis
point "d.0" you can set a value which corresponds to
the required output in the heating system in kW.
7.2.2 Setting the pump overrun time
The pump overrun time for the heating operation is set in
the factory to a value of 5 minutes. It can be set under
diagnosis point "1" within the range two minutes to
60 minutes. Under diagnosis point "d.18" you can set the
overrun behaviour of the pump to a different mode.
Overrun: After completion of the heat demand the heating
pump continues to run for the time set under "d.1".
Continuous: The internal heating pump is switched
on when the rotary knob for setting the heating feed
temperature is not in the left-hand stop position and the
heat demand is released by an external controller.
Winter: The internal heating pump is switched on when
the rotary knob for setting the heating feed temperature
is not in the left-hand stop position.
7.2.3 Setting the maximum flow temperature
The maximum feed temperature for the heating is set in
the factory to 75 °C. Under diagnosis point "d.71" it can
be set to between 40 und 85 °C.
7.2.4 Setting the return temperature control
When connecting underfloor heating or wall heating to
the appliance which does not have its own temperature
regulation, the temperature regulation mode can be
changed from feed temperature regulation (factory
setting) to return temperature regulation under
diagnosis point "d.17".
7 Adapting the appliance to the heating system