Selected output mode will be activated at next reset or power up.
Example:
smode poll
Serial mode : POLL
Set Serial Line Settings
Use the SERI command to set the serial line settings. The new settings
will be taken into use when the transmitter is reset or powered up.
Note that changing the serial line settings will slightly alter how the
transmitter works with the MI70 indicator. If you are not using the
default settings of 19200 N 8 1, you will have to power off the MI70
before it can find the transmitter (you will not be able to connect it on-
the-fly).
When using the Modbus protocol, the baud rate must be 9600 or higher.
SERI [b p d s]<cr>
where
b
=
baud rate (300, 600, 1200, 2400, 4800, 9600, or 19200)
p
=
parity (n = none, e = even, o = odd)
d
=
data bits (7 or 8)
s
=
stop bits (1 or 2)
Example:
seri 9600 e 7 1
Baud P D S : 9600 E 7 1
Set Transmitter Address
To operate in the POLL mode, the transmitter must have an address. If
multiple transmitters share the same serial line, each transmitter must
have a different address.
For a description of the serial interface modes, see section Set Serial Line
Operating Mode on page 41.
ADDR [address]<cr>
where
address
=
Transmitter address, range 0 ... 255.