Syntax Description
s<cr>
Stop the continuous outputting of
measurement values.
Example:
...
T= 22.8 'C RH= 39.5 %RH Td= 8.3 'C Tw= 14.5 'C h= 40.4 kJ/kg
T= 22.8 'C RH= 39.5 %RH Td= 8.3 'C Tw= 14.5 'C h= 40.4 kJ/kg
s
Table 12 S Command
Since the interface is half-duplex, you must enter the s command
when the device is not outputting.
Syntax Description
intv<cr>
Show the output interval of the automatically
repeating measurement messages (
r
command and run mode).
intv [iii u]<cr>
Set the output interval.
iii = interval, range 0 ... 255.
u = unit for interval setting:
n s =seconds
n m = minutes
n h = hours
If you set the interval to 0, the output
messages are output as quickly as they are
generated, without additional delay.
Example:
intv 5 s
Output interval: 5 S
Table 13 Intv Command
Measurement Output Format
Syntax Description
unit<cr>
Show current setting of the unit command.
unit [m|n]<cr>
Set types of units used on the serial line.
m = metric units, for example, Celsius
n = non-metric units, for example, Fahrenheit
Example (set units to non-metric):
unit n
Units : Non metric
Table 14 Unit Command
29
4 Service Port