Instruction Manual

HMP230 SERIES
M210225en-B User's Guide
47
6.4.1.2. Selecting and scaling the analogue output quantities
Disconnect the security lock jumper!
ASEL xxx yyy <cr>
xxx = channel 1's quantity
yyy = channel 2's quantity:
RH = relative humidity
T = temperature
Td = dewpoint temperature
Abs = absolute humidity
Mix = mixing ratio
h = enthalpy
Tw = wet bulb temperature
Example: relative humidity selected on channel 1 and temperature on channel
2
>ASEL RH T <cr>
Ch1(RH) lo 0.000 %RH ? <cr>
Ch1(RH) hi 100.000 %RH ? <cr>
Ch2(T ) lo -40.000 'C ? <cr>
Ch2(T ) hi +160.000 'C ? <cr>
6.4.1.3. Scaling the analogue outputs
Disconnect the security lock jumper!
ASCL <cr>
Example: relative humidity is scaled on the range of 0...100 %RH and tem-
perature -40...+160 °C
>ASCL <cr>
Ch1(RH) lo 0.000 %RH ? <cr>
Ch1(RH) hi 100.000 %RH ? <cr>
Ch2(T ) lo 0.000 'C ? -40 <cr>
Ch2(T ) hi 100.000 'C ? 160 <cr>