Specifications

45
60/70 Series Duct & Wall-Mount Humidity
& Temperature Transmitters for HVAC/EMCS
FEATURES/BENEFITS
 Full 0...100 %RH measurement
True two-wire transmitters with 4...20 mA loop
powered output (HMD 60 and HMW 60)
 Selectable signal output of 0...1 V, 0...5 V or
0...10 V (HMD 70 and HMW 70) with optional
current module also 0...20 mA (HMD 70)
Electromagnetically compatible
Temperature compensated
Excellent long-term stability
Up to ± 2 %RH accuracy
HUMICAP
®
humidity sensor for excellent accuracy
and long-term stability, negligible hysteresis and
resistance to dust and most chemicals.
 ±2% RH accuracy (0...90%)
±3% RH accuracy (90...100%)
NEMA 4 housing (duct unit only)
Also available as temperature-only transmitters
HMD/W 60T/70T
OPTIMAL ENERGY MANAGEMENT
The duct and wall-mounted HMD/W 60 and
HMD/W 70 transmitters are designed for monitoring
relative humidity and temperature in building energy
management systems. The combination of high
accuracy, stability and reliable operation makes these
products the ideal choice for demanding energy
management applications.
The duct mount transmitters can also be used in
many industrial humidity monitoring applications,
where their stability and resistance to chemicals and
dust are of great value.
A novel feature of these duct mount transmitters is
the ability to remove the electronics without disas-
sembling the unit from the duct.
The HMD/W 60 and HMD/W 70 transmitters are
available in three models: U for humidity
measurement-only, Y for humidity and temperature
measurement, and T for temperature only.
FAST, ON-SITE CALIBRATION
The accuracy of the transmitters is simple to check
using the HMI 41 humidity calibrator. The calibration
can be done in seconds with a single potentiometer
without disturbing operation. This saves hours of
maintenance time and ensures high system accuracy.
HMD 60 or 70
HMW 60 or 70
110 (4.33)
85 (3.35)
33 (1.30)
Ø 12
(0.47)
250 (9.84)62 (2.44)
100 (3.94)
<<< Mounting hole 82 (3.23)
100 (3.94)
Mounting hole 82 (3.23)
>>>