Type the percentage value using the numeric keypad and then press the [ENTER]
key. Continue to step e.
2. DIST FROM CLOSE
Press the [2] key (DIST FROM CLOSE) to set the open analysis point #1 as a distance
from the contact’s close position.
NOTE
The distance from close range is selectable from 00.0 inch to 99.99 inches or
from 0.0 to 999.0 millimeters. The distance is referenced from the contact’s
closed position.
The following screen will be displayed:
Type the distance value using the numeric keypad and then press the [ENTER] key.
Continue to step e.
3. CONTACT #1
Press the [3] key (CONTACT #1) to set the open analysis point #1 value equal to the
contact point #1 value. Continue to step e.
NOTE
Contact point #1 is the distance from the contact’s closed position to the
point where it is in transition from the CLOSE to OPEN or the OPEN to CLOSE
position.
OPEN ANALYSIS PT 1
DISTANCE FROM CLOSE
VALUE: 025.4 mm
“ENTER” TO CONFIRM
OPEN ANALYSIS PT 1
% OF TOTAL STROKE
VALUE: 00%
“ENTER” TO CONFIRM