Owner's manual

CT-7500 S2 USER’S MANUAL REV 2
77
3.4 Working With Test Plans
The CT-7500 S2 comes with the Vanguard Circuit Breaker Analysis S2 (VCBA S2) PC Software
that can be used to create circuit breaker test plans. The test plans can then be transferred to
the CT-7500 S2. The CT-7500 S2 can store up to 99 circuit breaker test plans in its Flash
EEPROM.
A circuit breaker test plan contains breaker maximum/minimum parameters and can be used to
quickly test a breaker. A typical list of operating parameters in a test plan includes the
following:
Max/Min Contact/Resistor Trip Time
Max/Min Contact/Resistor CLOSE time
Max Contact Spread Time
Max Resistor Contact Spread Time
Max/Min Contact CLOSE-OPEN Time
Max/Min Contact OPEN-CLOSE Time
Max/Min Resistor CLOSE-OPEN Time
Max/Min Resistor OPEN-CLOSE Time
Max/Min Breaker Stroke
Max/Min Breaker Trip Velocity
Max/Min Breaker CLOSE Velocity
Max/Min Breaker Over-Travel
Max/Min Breaker Bounce-Back
Trip Velocity Analysis Calculation Points
CLOSE Velocity Analysis Calculation Points
If a timing test is executed with a breaker test plan, the timing report will display a Pass/Fail
indicator for each of the parameters tested. The Pass/Fail status is determined by comparing
the values in the test plan to the timing test results.
3.4.1. Recalling a Breaker Test Plan for Use
Use the steps below to recall a breaker test plan to use for a timing test:
a. Start from the “START-UP” menu:
Press the
[3] key (SETUP).
1. TIME BRKR 02/10/11
2. GET RSLT 15:14:13
3. SETUP
4. DIAGNOSTICS