Owner's manual

CT-7500 S2 USER’S MANUAL REV 2
89
4.3 Testing the Cable Hookups
You can check the CT-7500 S2 contact cable connections to the circuit breaker using the steps
below:
a. Start from the “START-UP” menu:
Press the [4] key (DIAGNOSTICS).
b. The following screen will be displayed:
Press the [2] key (CHECK HOOKUP).
c. The following screen will be displayed:
Make sure the breaker is in the CLOSED position and then press the [START] key.
d. The screen will be updated to show the status of each contact as shown:
A report will also be printed on the thermal printer showing the status of each contact.
A contact closure is shown as “C” on the screen and on the printout. An open contact is
shown as “-” on the screen and on the printout.
Press the [START] key to retest the cable connections, or press the [STOP] key to
end the test and return to the “START-UP” menu.
1 2 3
C - -
“START” to RETEST
“STOP” to EXIT
MAKE SURE BREAKER IS
IN CLOSED POSITION
THEN PRESS “START”
1. SLOW CLOSE TEST
2. CHECK HOOKUP
3. TEST TRANSDUCER
4. NEXT PAGE
1. TIME BRKR 02/14/11
2. GET RSLT 09:55:00
3. SETUP
4. DIAGNOSTICS