SHR Series Woodburning Fireplace Homeowner's Installation and Operating Manual For Models: SHR36 SHR42A SHR48 SHR52 1384 SHR cover 5/27/99 djt Underwriter's Laboratories Report No. MH6018 DO NOT DISCARD THIS MANUAL: Retain for future use. 20001384 12/06 Rev.
SHR Series Woodburning Fireplace Safety Information PLEASE READ THIS MANUAL BEFORE INSTALLING AND USING FIREPLACE. IMPORTANT: Read all instructions and warnings carefully before starting installation. Failure to follow these instructions may result in a possible fire hazard and will void the warranty. Description The SHR Series fireplaces are solid fuel, woodburning fireplaces. The SHR36/42A/48 (Super Hearth) are clean-face fireplaces.
SHR Series Woodburning Fireplaces SHR36 Series Woodburning Fireplace Rough Opening Depth 57�����" (1472mm) 13���" Dia. (340mm) 11" Dia.
SHR Series Woodburning Fireplace SHR48 Series Woodburning Fireplace Rough Opening Depth 66���" (1686mm) 11" Dia. (279mm) m "( m m ) 23 84 m Rough Opening Height Rough Opening Width 59���" (1518mm) 15���" (397mm) 13���" (349mm) 7���" (197mm) 48���" (1232mm) Outside Air 53" (1346mm) �� ��� 19 13���" Dia.
SHR Series Woodburning Fireplaces B SHR36 SHR42A C SHR48 A SHR52 FP1531 Front Width A 35³⁄₄" (908 mm) 41⁷⁄₈" (1064 mm) 47³⁄₄" (1213 mm) 52" (1321 mm) Back Width B 22" (559 mm) 26⁵⁄₈" (676 mm) 34" (864 mm) 34¹⁄₂" (876 mm) Depth C 20³⁄₈" (516 mm) 23³⁄₈" (594 mm) 20¹⁄₄" (514 mm) 25¹⁄₄" (641 mm) Fig. 4a Hearth dimensions. FP1531 hearth dimensions Chase Installation djt Insulation methods shown9/04 are optional for cold climate, not a requirement for unit operation.
SHR Series Woodburning Fireplace Chimney Requirements - Offset Installations Offset Chimney Flue Exit Rise Chimney Section FP282 B A 30˚ Elbow OffsetsIWF282 30° Return Elbow G 1' 1¹⁄₂' 3' 4' G D E 6 FT. C 30° Offset Elbow Rise 30° Return Elbow H Offset 30° Offset Elbow B 11CS Support H Hearth Floor Example 1 Example 2 Notes: G + H cannot exceed 20 feet. *11CF Chimney airspace clearance = 2" minimum. Illustration Key A.
SHR Series Woodburning Fireplaces Planning Information Preplanning an installation is very important to ensure safety and to save time and money. An installer must predetermine where a fireplace will be set and how the chimney system will be run. Mounting the Fireplace A fireplace may only be mounted on the following surfaces: 1. A flat combustible surface. 2. A raised wooden platform. 3. A concrete block or other solid object placed beneath each of the four (4) corners of the fireplace.
SHR Series Woodburning Fireplace Installation Chimney Supports The chimney system is supported by the fireplace for vertical chimney heights less than 30 feet above the hearth. Chimney supports are required if the vertical height exceeds 30 feet with 11CF chimneys. Locate chimney supports at ceiling holes or other structural framing at 30 foot heights. Spacing between chimney supports must not exceed 30 feet. Use Chimney Support Model 11CS. (NOTE: The 11CS can not be mounted directly to the fireplace.
SHR Series Woodburning Fireplaces Rear Firebrick Brick Retainer Hard, Flat Surface Side Firebrick Front Notch FP1234 Fig. 11 SHR52 Firebrick installation. Insulation 3. Slide the rear firebrick back into the left corner behind the end of the left firebrick. FP1234Push both panels back as far as possible into the left side and corner. SHR52 4. Swing the right side of the back firebrick into place.
SHR Series Woodburning Fireplace CAUTION: REPORT TO YOUR DEALER ANY PARTS DAMAGED IN SHIPMENT, SPECIFICALLY CHECK THE END CONNECTION OF CHIMNEY SECTIONS AND ELBOWS. Chimney Centerline Actual Centerpoint NOTE: SHR Series Fireplaces must use CFM Corporation model 11CF, 11 inch, 2 wall chimney systems. The installation procedure described in this manual applies only to the 11CF system, chimney components may not be mixed.
SHR Series Woodburning Fireplaces The inside dimension of the frame must be the same as the hole size selected from Figure 11 in order to provide the required 2 inches of air space between the outside diameter of the chimney and the edges of the framed ceiling hole. Existing Ceiling Joists 17¹⁄₂" (445 mm) Metal Safety Strips (1, 2 or 3 pieces) 17¹⁄₂" (445 mm) Fireplace Chimney Hole ����" 1/2" Min. Overlap Platform "Z" Safety Strip (not supplied) Hearth Ext. FP557a Fig.
SHR Series Woodburning Fireplace Support Structure Open Closed Elbow Strap (must be tight) ELBOW STRAP Angle Firestop FP710a Fig. 18 Outside air operation. ANGLED STRAP Installing the Chimney System Start by attaching the first chimney section to the collar on top of the fireplace. FP710a OUTSIDE AIR Install the pipe as SHR pictured inLEVER Figure 19. When you WOOD FIREPLACES 10/21/99 get a good lock, you will hear the pipe clearly snap together.
SHR Series Woodburning Fireplaces Ceiling Installation Attic Installation Nails (4) Joist Firestop Spacer Firestop Spacer Joist Flange Down Into Hole Nails (4) Flange Up Into Hole FP285 Fig. 21 Installing firestop spacer.
SHR Series Woodburning Fireplace Installing Chimney in a Chase Air Space Clearances Combustible framing material MUST NOT penetrate AIR SPACE (shaded areas) Refer to Page 5, Figure 4 for an illustration of a typical chase installation. CAUTION: Treatment of firestop spacers and construction of chase may vary with type of building. These instructions are not a substitute for local building codes. You must check your local building codes to determine specific requirements for your city or state.
SHR Series Woodburning Fireplaces Mantel Clearance with Noncombustibel Facing Material Mantel Clearance No Noncombustible Facing Material 12" (305mm) Max. Combustible Mantel and Trim 1���" Combustible Mantel and Trim Finished Wall Header * Minimum width from top of surround to bottom of screen rail Finished Wall Header 1���" Ledge Bracket 12" (305mm) min. Ledge Bracket Noncombustible Material 12" (305mm) min. Noncombustible Material * 12" (305mm) Max. Surround Face 6" (159mm) Min.
SHR Series Woodburning Fireplace Stud Finished Wall Noncombustible Decorative Facing 2 x 4 Finished Header Covered Wall Must be Sealed with Noncombustible Material CAUTION: Do Not Place Finishing Material Beyond These Edges or Cover Air Inlets Ledge Bracket Surround Hearth FP1168 FP1167 Fig. 26 Facing on fireplace surround flush with finished wall. Screen Rail Fig. 27 Finishing front of fireplace.
SHR Series Woodburning Fireplaces Side Wall Protection Adjacent combustible side walls that are within dimensions shown in Figure 29 of fireplace opening must be protected with Wall Shield Model SP40 or a specifically built wall shield described in Figure 28. The special wall shield design described in Figure 26 is an alternate method of adding protection to side walls and can be used in place of the SP40 with the same wall clearances specified for the SP40. Rt must =1.85 minimum.
SHR Series Woodburning Fireplace Minimum Hearth Extension Dimensions Minimum Wall Clearances WITH Noncombustible Surround Facing WITHOUT Noncombustible Surround Facing Shaded area starts 1/2" away from edge of unit 4" 4" Brick (Example material) E Firebox Opening F** E D A - Min. clearance to combustible perpendicular wall C** Side Wall Side B - Min. clearance Wall to combustible perpendicular wall when using noncombustible wall shield* Combustible material permitted within shaded area.
SHR Series Woodburning Fireplaces Wall Covering 2 x 4 Header - Do Not Notch at Ledge Brackets Fig. 22 or 23 Hearth Extension Hearth Extension Insulation Molding used to Fasten Hearth Extension in Place Majestic Safety Strips Must be Overlapped 1/2" Min. FP1171 Seal Crack Between Fireplace and Hearth Extension with Noncombustible Material Fig. 33 Sealing detail.
SHR Series Woodburning Fireplace 12 13 2 7 1 b c 8 d a 6 9 5 4 3 10 11 CFM Corporation reserves the right to make changes in design, materials, specifications, prices and discontinue colors and products at any time, without notice. SHR36/42A/48/52 Woodburning Fireplace For units FH30RO, GH40RO, HH30RO, IH10RO 1384 pts 1. 2. 3. 4. 5. 6. 7. 8a. 8b. 8c. 8d. 9. 10. 11. 12. 13.
SHR Series Woodburning Fireplaces Accessories The following accessories for this appliance are available from your local Majestic Fireplaces distributor. Should you need additional information beyond what your distributor can furnish, contact: CFM Corporation, 2695 Meadowvale Blvd., Mississauga, Ontario, Canada L5N 8A3 Attn: Technical Services. CAUTION: This fireplace and chimney assembly is a highly engineered system, and, as such, must be operated only with CFM Corporation approved components.
SHR Series Woodburning Fireplace Accessory Description Contemporary Flashing Required for contemporary top termination on the roof to prevent rain entry. 8-6-12 (0 to 6/12 pitch) 8-12-12 (6/12 to 12/12 pitch) Contemporary Chase Top Termination Used to terminate chimney at the top of a chase. Adapter kit is included, flashing is not included. SLTCF11 Contemporary Round Top Termination For use with CFM Corporation Type "11CF" Chimney Systems. Used to terminate chimney on the roof.
SHR Series Woodburning Fireplaces � LIMITED WARRANTY & 30 YEAR PROTECTION PLAN For MAJESTIC FIREPLACES® PRE-ENGINEERED Fireplace Systems CFM Corporation warrants its MAJESTIC FIREPLACES® Pre-Engineered Fireplace (“Fireplace”) and the CFM Corporation supplied firegrate, glass doors, outside air system, fan motor, and liners to be free from defects in material or workmanship, as follows: A.