1.2.3 Setting the dome protocol
• Set sections 1,2 and 3 of the 6-way switch (B) as per the table below to select the
required protocol. “0” represents OFF (down) and “1” represents ON (up).
Protocol 1 2 3
Videoswitch VXP4 and BBV up-the-coax 0 0 0
Videoswitch VXP4 only 1 0 0
PelcoP 0 1 0
PelcoD 1 1 0
Vista 0 0 1
spare 1 0 1
spare 0 1 1
spare 1 1 1
If coax telemetry is not being used, a protocol other than the first one should be selected to
minimise the possibility of spurious commands being received.
1.2.4 Setting the baud rate
• Set sections 4 and 5 of the 6-way switch (B) as per the table below to select the
required baud rate. “0” represents OFF (down) and “1” represents ON (up).
• The default setting is 9600 baud (both switches OFF)
• PelcoD normally uses 2400 baud
• PelcoP normally uses 4800 baud
Baud rate 4 5
9600 0 0
2400 1 0
4800 0 1
19200 1 1