Installation Guide

Table Of Contents
Product Information
16 of 44
IM-PP 724607 0320 ProPress
2.5.5 Underground Installations
Viega ProPress 󶈵tting systems with copper tubing are approved for
underground installations. However, installations must meet all state and
local codes, including those for underground. Proper authorization must
be obtained prior to installation from the Authority Having Jurisdiction.
Viega ProPress 󶈵ttings exposed to corrosive action, such as soil
conditions or moisture, must be protected in an approved manner in
accordance with NFPA 54 Section 404.8, NACE Standard RP0169-2002
Section 5, 2009 UPC Chapter 6 Section 609.3.1, 2009 UMC Chapter
13 Section 1312.1.3, or satisfying local code requirements. In addition,
systems should be properly sized to minimize the risk of erosion corrosion
resulting from excessive velocities.
In water installations, mixed metal systems can have a detrimental
e󶈴ect on each other and cause corrosion.
Copper tubing should not be installed directly upstream from
galvanized steel pipe.
Dielectric unions should be used when connecting copper to steel or
galvanized steel pipe.
Care should be taken to select hangers of suitable material that are
galvanically compatible with the tubing.
Above ground copper tubing and 󶈵ttings do not normally require external
corrosion protection with the following exceptions:
Contact with aggressive building materials such as nitrite or materials
containing ammonium.
In aggressive environments.
Please contact the Viega Technical Services Department for questions on
this subject.
The 󶈶ow rule must be observed in all mixed installations
with tubing made of copper and pipes made of galvanized
steel.
2.5.6 Concealed Spaces
The Viega ProPress 󶈵tting system has been approved for use in
concealed spaces. Speci󶈵c performance tests were conducted to
evaluate the 󶈵ttings for use in concealed spaces. Concealed tubing and
󶈵ttings shall be protected from puncture threats.
2.5.7 Corrosion Protection
2.5.7.1 Mixed Installations