For hard copper tubing in ½" to 2" and soft copper tubing in ½" to 1¼".
Check the sealing element for correct 󶈵t:
The tube end is not bent or damaged.
The tube is deburred.
The correct sealing element is in the 󶈵tting.
The sealing element is undamaged.
The complete sealing element is in the bead.
Measure insertion depth (see table below).
Mark the proper insertion depth on the outside of the tube.
Improper insertion depth
Improper insertion depth may result in an improper seal.
Be sure to mark the correct insertion depth on the tube
before pressing the 󶈵tting.
Tube Diameter (inches) Insertion Depth (inches)
½ ¾
¾
1
1
1
7
/
16
2 1
9
/
16
Table 18: Minimum insertion depths for ProPress ½" to 2" 󶈵ttings
4.8 Pressing the Fitting
WARNING!
Read and understand all instructions for
installing Viega ProPress 󶈵ttings. Failure to
follow all instructions may result in extensive
property damage, serious injury, or death.
4.8.1 Viega ProPress ½" to 2" Installation