Installation Guide

Table Of Contents
Installation Instructions
34 of 44
IM-PP 724607 0320 ProPress
For hard copper tubing in 2½" to 4".
4.8.2 Viega ProPress 2½" to 4" Installation
WARNING!
Read and understand all instructions for
installing Viega ProPress 2½" to 4" 󶈵ttings.
Failure to follow all instructions may result in
extensive property damage, serious injury, or
death.
Use only rings that are compatible with ProPress
2½" to 4" 󶈵ttings.
Use of incompatible rings will result in an improper
connection.
Do not mix actuators and rings from di󶈴erent
manufacturers.
Do not use rings intended for XL Bronze 󶈵ttings.
Check the sealing element, separator ring, and grip ring for correct 󶈵t:
The tube end is not bent or damaged.
The tube is deburred.
The correct sealing element is in the 󶈵tting.
Illustration demonstrates proper 󶈵t of grip ring, separator ring, and sealing
element.