Installation Guide
Table Of Contents
- About this Document
- Disclaimer
- Product Information
- Handling Instructions
- Installation Instructions
- Limited Warranty
- ProPress approved applications
- Minimum distance between press fittings
- ProPress standard jaws clearance requirements
- ProPress standard jaws clearance requirements between tube, wall, and floor
- ProPress compact jaws clearance requirements
- ProPress compact jaws clearance requirements between tube, wall, and floor
- ProPress rings dimensions
- ProPress rings with V1 Actuator clearance requirements
- ProPress rings with V2 Actuator clearance requirements
- ProPress rings with V1 Actuator clearance requirements between tube, wall, and floor
- ProPress rings with V2 Actuator clearance requirements between tube, wall, and floor
- ProPress rings with C1 Actuator clearance requirements between tube, wall, and floor
- ProPress XL-C rings dimensions
- ProPress XL-C rings clearance requirements
- ProPress XL-C rings clearance requirements between tube, wall, and floor
- Minimum distance between existing soldered or brazed fitting and ProPress fitting
- Minimum distance between existing ProPress fitting and soldered or brazed fitting
- Minimum insertion depths for ProPress ½" to 2" fittings
- Insertion depths for ProPress ½" to 2" no-stop couplings
- Insertion depths for ProPress ½" to 2" extended no-stop couplings
- Minimum insertion depths ProPress 2½" to 4" fittings
- Insertion depths for ProPress 2½" to 4" no-stop couplings
Installation Instructions
29 of 44
IM-PP 724607 0320 ProPress
Tube
Diameter
(inches)
Soldering
minimum
distance (inches)
Soldering
minimum
distance (mm)
Brazing minimum
distance (inches)
Brazing minimum
distance (mm)
½ 1½ 38 4½ 114
¾ 2¼ 57 6¾ 172
1 3 76 9 229
1¼ 3¾ 95 11¼ 286
1½ 4½ 114 13½ 343
2 6 153 18 457
2½ 7½ 191 22½ 572
3 9 229 27 686
4 12 305 36 915
Table 17: Minimum distance between existing ProPress tting and soldered or brazed tting
The installer should take precautions to keep the Viega ProPress
connection cool:
■ Wrap the connection with a cold wet rag.
■ Protect the connection with a weld blanket.
■ Prefabricate solder connections/welded ttings prior to installing the
press tting. (Ensure tube has cooled before installing the tting).
■ Apply heat sink gel or spray or spot freezing
4.5 Welding
To prevent damage to the sealing element, maintain proper welding
distances from the tting. If welding adjacent to the connection, weld a
minimum of four inches away.
Installers should follow the precautions listed above to keep the Viega
ProPress connection cool.