Installation Guide
Table Of Contents
- About this Document
- Disclaimer
- Product Information
- Handling Instructions
- Installation Instructions
- Limited Warranty
- ProPress approved applications
- Minimum distance between press fittings
- ProPress standard jaws clearance requirements
- ProPress standard jaws clearance requirements between tube, wall, and floor
- ProPress compact jaws clearance requirements
- ProPress compact jaws clearance requirements between tube, wall, and floor
- ProPress rings dimensions
- ProPress rings with V1 Actuator clearance requirements
- ProPress rings with V2 Actuator clearance requirements
- ProPress rings with V1 Actuator clearance requirements between tube, wall, and floor
- ProPress rings with V2 Actuator clearance requirements between tube, wall, and floor
- ProPress rings with C1 Actuator clearance requirements between tube, wall, and floor
- ProPress XL-C rings dimensions
- ProPress XL-C rings clearance requirements
- ProPress XL-C rings clearance requirements between tube, wall, and floor
- Minimum distance between existing soldered or brazed fitting and ProPress fitting
- Minimum distance between existing ProPress fitting and soldered or brazed fitting
- Minimum insertion depths for ProPress ½" to 2" fittings
- Insertion depths for ProPress ½" to 2" no-stop couplings
- Insertion depths for ProPress ½" to 2" extended no-stop couplings
- Minimum insertion depths ProPress 2½" to 4" fittings
- Insertion depths for ProPress 2½" to 4" no-stop couplings
Installation Instructions
37 of 44
IM-PP 724607 0320 ProPress
4.9 Pressure Testing
Viega Smart Connect technology provides a quick and easy way for
installers to identify connections that need to be pressed. Unpressed
connections are located by pressurizing the system with air or water.
Pressure test all installed tube in accordance with local codes.
Smart Connect Testing
■ Testing for unpressed connections using Smart Connect
is not a replacement for pressure testing requirements
of local codes and standards.
■ If testing with compressed air, use an approved leak-
detect solution.
Water testing with Viega Smart Connect:
■ Use a range of 15 to 85 psi.
■ If an unpressed tting is found, make sure the tube is fully inserted
before completing the press.
■ If the initial test is successful, system may be pressure tested as
required up to 600 psi.
Testing with air can be dangerous at high pressures. When air testing with
Viega Smart Connect:
■ Use a range of ½ psi to 45 psi.
■ If an unpressed tting is found, make sure the tube is fully inserted
before completing the press.
■ If the initial test is successful, system may be pressure tested as
required up to 200 psi.