Unit installation

18
3. If the CO
2
content must be adjusted:
Remove cover B.
Turn adjusting screw A in small
increments (Torx 40) until the CO
2
content falls within the specified
range:
Turning clockwise
→ CO
2
content rises
Turning anti-clockwise
→ CO
2
content falls
4. Record the actual value in the report
(on page 61).
Rechecking the values
Regulate to the upper and lower heat-
ing output using the programming
unit in the burner control unit. If the
values do not match the permissible
CO
2
content according to the table on
page 16, repeat the steps for the
upper and lower heating output.
5.
Press "S" E and "-" D simultane-
ously. The burner is now in operating
mode.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5692 907 GB