Unit installation

36
DIP switch setting or parameter set
The DIP switch (at the back of the display and programming unit) is factory-set to the
rated heating output of the burner. A change to this factory setting is only required
for operation with reduced heating output.
Note
If another parameter set is selected, this must be acknowledged (see page 37).
Setting
Rated burner heating output
Setting
Reduced burner heating output
Parameter set 0
87 kW
1 2 3 4 5 6 7 8
ON
Parameter set 6
Not possible
Parameter set 1
115 kW
1 2 3 4 5 6 7 8
ONON
Parameter set 7
Not possible
Parameter set 2
142 kW
1 2 3 4 5 6 7 8
ONON
Parameter set 8
100 kW
1 2 3 4 5 6 7 8
ONON
Parameter set 3
186 kW
1 2 3 4 5 6 7 8
ONON
Parameter set 9
130 kW
1 2 3 4 5 6 7 8
ONON
Burner control unit
(cont.)
5692 907 GB