Unit installation

62
Note
Observing the following requirements is
necessary to safeguard your warranty
rights.
The manufacturer's warranty excludes
damage due to corrosion and scaling.
Prevention of damage due to scaling
Prevent excessive scale build-up (calcium carbonate) on the heating surfaces. For
heating systems with operating temperatures up to 100 °C, the VDI Directive 2035
sheet 1 "Prevention of heating system damage scaling in DHW and hot water heat-
ing systems" applies [in Germany] together with the following standard values (see
also the relevant explanations in the original directive).
Total heating output
kW
Total of alkaline earths
mol/m
3
Total hardness
°dH
> 50 to 200 ≤ 2.0 ≤ 11.2
> 200 to 600 ≤ 1.5 ≤ 8.4
> 600 < 0.02 < 0.11
The standard values assume the follow-
ing:
The total volume of fill and top-up
water during the system's service life
will not exceed three times the water
content of the heating system.
The specific system volume is less
than 20 l/kW heating output. In multi
boiler systems, apply the output of the
smallest boiler.
All measures to prevent corrosion on
the water side in accordance with VDI
2035 sheet 2 have been implemented.
Soften the fill and top-up water in heating
systems operating under the following
conditions:
The total of alkaline earths in the fill &
top-up water exceeds the standard
value.
Higher fill and top-up water volumes
are expected.
The specific system volume is higher
than 20 l/kW heating output. In multi
boiler systems, apply the output of the
smallest boiler.
Water quality requirements
5692 907 GB